ZGS11-H(Z) Combined Transformer
Type & Meaning

| Z | Combined Transformer |
| G | Common Tank Type |
| S | Three-Phase |
| 11 | Performance Level Code |
| H(Z) | High-Voltage Wiring Mode: H for Looped Network Type, Z for Terminal Type |
| □ | Rated Capacity (kVA) |
| □ | Voltage Class (kV) |
Applicable Standards
◇ JB/T10217-2000 Combined Transformers
◇ GB1094.1~2-1996 Power Transformers
◇ GB3804-1990 AC High-Voltage Load Switches for 3~63kV
◇ GB7251.1-1997 Low-Voltage Switchgear and Controlgear – Part 1: Type-Tested and Partially Type-Tested Assemblies
product Display
Technical Parameters
Technical Parameters of ZGS11-H(Z)-200~1000/10 Combined Transformer
| Rated Capacity (kVA) | Voltage Combination (kV) | Connection Symbol | No-Load Loss (W) | Load Loss (W) | Short-Circuit Impedance (%) | No-Load Current (%) | Weight (kg) | Overall Dimensions (mm) | High-Voltage Wiring Mode | ||||
| High Voltage | Tap (%) | Low Voltage | Body Weight | Oil Weight | Total Weight | L×W×H | |||||||
| 200 | 10 | ±2× 2.5 |
0.4 | Yyn0 Or Dyn11 |
335 | 2600 | 4.0 | 0.60 | 601 | 733 | 1894 | 1865×1240×1735 | Looped Network Type (H) or Terminal Type (Z) |
| 250 | 390 | 3050 | 0.50 | 716 | 749 | 2060 | 1865×1280×1735 | ||||||
| 315 | 465 | 3650 | 0.45 | 835 | 733 | 2148 | 1865×1730×1735 | ||||||
| 400 | 560 | 4300 | 0.40 | 1006 | 729 | 2375 | 1865×1440×1805 | ||||||
| 500 | 670 | 5100 | 0.40 | 1156 | 747 | 2603 | 1865×1450×1805 | ||||||
| 630 | 840 | 6200 | 4.5 | 0.40 | 1295 | 757 | 2826 | 1865×1450×1860 | |||||
| 800 | 980 | 7500 | 0.40 | 1521 | 872 | 3357 | 1865×1495×1860 | ||||||
| 1000 | 1190 | 10300 | 0.30 | 1634 | 970 | 3704 | 1865×1510×1860 | ||||||
Note: The weight and overall dimension data in the table are for reference only; no prior notice will be given for any changes.
Product Features
◇ Compared with Type "9" transformers, this product reduces no-load loss by 30.12% and average annual operating cost by 20.03%, with low noise, making it an environmentally friendly product.
◇ The transformer body, high-voltage load switch (or high-voltage load transfer switch), fuses, off-circuit tap-changer, etc., are all placed in a fully sealed oil tank, improving space utilization. Its volume is only about 1/3 of that of combined substations (also known as European-style substations) of the same voltage class and capacity, and the weight is also greatly reduced.
◇ High-voltage and low-voltage compartments are isolated and interlocked: the high-voltage compartment door can only be opened after the low-voltage compartment door is opened, and high-voltage terminals are fully insulated, ensuring high safety.
◇ It adopts a full-range protection method combining two-stage fuses (backup current-limiting fuses and plug-in fuses), which is safe and reliable, flexible in operation and convenient for fuse replacement.
◇ The oil tank is of fully sealed structure, isolating the oil inside from the outside, with no leakage and maintenance-free.