XGN15-24 Medium Voltage Switchgear SF6 Insulated Ring Main Unit - China Suppliers Factory for Reliable Power Distribution
Type Designation

| No. | Description |
| 1 | Box-type Construction |
| 2 | Fixed Type |
| 3 | Indoor Type |
| 4 | Design Serial Number |
| 5 | Rated Voltage kV |
| 6 | Rated Current A |
| 7 | I: FLN36-12 Load Switch | Ⅱ: FLN48-12 Load Switch |
Technical Parameters
| No. | Parameter | Unit | Value |
| 1 | Rated Voltage | kV | 12 |
| 2 | Rated Frequency | Hz | 50 |
| 3 | Main Busbar Rated Current / Maximum Fuse Rating | A | 630, 125 |
| 4 | Main Circuit & Earth Circuit Rated Short-time Withstand Current | kA/S | 20/3 |
| 5 | Main Circuit & Earth Circuit Rated Peak Withstand Current | kA | 50 |
| 6 | Main Circuit & Earth Circuit Rated Short-circuit Making Current | kA | 50 |
| 7 | Load Switch Full-capacity Breaking Operations | operations | 100 |
| 8 | Fuse Breaking Capacity | kA | 31.5, 40 |
| 9 | Rated Closed-loop Breaking Current | A | 630 |
| 10 | Rated Transfer Current | A | 1600 |
| 11 | Mechanical Endurance | operations | 2000 |
| 12 | 1-minute Power Frequency Withstand Voltage (phase-to-phase / earth / isolation) | kV | 42, 48 |
| 13 | Lightning Impulse Withstand Voltage (phase-to-phase / earth / isolation) | kV | 75, 85 |
| 14 | Secondary Circuit 1-minute Power Frequency Withstand Voltage | kV | 2 |
| 15 | Protection Class | — | IP3X |
Product Display
Environmental Conditions
- Altitude: no more than 2000m
- Ambient temperature: minimum temperature −25°C; The highest temperature is +40°C
- Ambient humidity: daily average value shall not exceed 95%; The monthly average value shall not exceed 90%
- Seismic capacity: Grade 8
- The surrounding air is free of explosive and corrosive gases, and the installation site is free of violent vibration and impact
Schematic Diagram

| 1. Operating Mechanism | 4. Instrument Compartment | 7. Fuse |
| 2. Load Switch | 5. SF6 Voltage Meter | 8. Lower Grounding Switch |
| 3. Cabinet Body | 6. High-voltage Live Display |
Auxiliary Equipment

- Fault Indicator: The DJD-1 short-circuit grounding fault indicator uses logic circuits for over-current alerts and manual reset, with sensors on cables and a display unit for quick fault detection.
- Condensation Controller: This device monitors temperature/humidity in real-time, activating heaters at 85%RH to prevent condensation (rated power: 75–100W).
- FTU & Communication: The DAT-1L automation terminal enables SCADA integration with 48 remote signaling channels, self-diagnosis, and multi-protocol support (IEC101, MODBUS, etc.).
- Current Limiting Fuse: Designed for 24kV/50Hz systems (292mm length), it protects indoor switchgear from overcurrent faults.
Frequently Asked Questions
What is the rated voltage of the XGN15-24 Medium Voltage Switchgear?
The XGN15-24 is rated at 12kV with a rated frequency of 50Hz. It is designed for indoor, fixed-type, box-construction installations in medium voltage distribution systems.
What types of load switches are compatible with the XGN15-24?
The XGN15-24 supports two load switch types: Type I uses the FLN36-12 Load Switch, and Type II uses the FLN48-12 Load Switch, offering flexibility for different application requirements.
What are the environmental requirements for installing the XGN15-24 switchgear?
The switchgear should be installed at altitudes no greater than 2000m, with ambient temperatures between −25°C and +40°C. Daily humidity must not exceed 95% and monthly average humidity must not exceed 90%. The seismic capacity is Grade 8, and the environment must be free of explosive/corrosive gases and severe vibration.
What is the protection class and mechanical endurance of the XGN15-24?
The XGN15-24 carries a protection class of IP3X to protect against solid particle ingress. Its mechanical endurance is rated at 2,000 operations, ensuring long-term reliability in demanding power distribution environments.
Does the XGN15-24 support SCADA or remote monitoring integration?
Yes. The optional DAT-1L FTU (Feeder Terminal Unit) enables full SCADA system integration with 48 remote signaling channels, built-in self-diagnosis, and support for multiple communication protocols including IEC101 and MODBUS.
What auxiliary protection devices are available for the XGN15-24 switchgear?
Key auxiliary equipment includes the DJD-1 Fault Indicator for over-current detection, a Condensation Controller that activates heaters at 85%RH to prevent moisture damage, and a Current Limiting Fuse designed for 24kV/50Hz systems (292mm length) to protect against overcurrent faults.