SM6 Modular Air Insulated Medium Voltage Ring Main Unit (RMU)

The SM6 medium voltage ring main unit is designed for indoor installation in power distribution rooms and container substations, with front cable wiring. Its dimension range: width 375–750mm, height 1600–2050mm, fixed depth 840mm. All control components are centralized on the front operation panel for easy operation, compatible with relays, coils, instrument transformers and other accessories. Rated for 12kV/24kV/36kV, it features E3 class making-breaking capacity, 630A-1250A rated load breaking current and reliable short-circuit withstand performance. It works stably within defined temperature, altitude, humidity and pollution limits without direct sunlight exposure.

    Normal Operating Conditions

    Ambient Temperature: Max 40°C, 24h average ≤35°C, min -25°C
    Altitude: 12kV model: ≤2000m; 24kV model: ≤1000m. Derating needed for higher altitudes, contact us.
    Sunlight: No direct sunlight exposure.
    Environment: No heavy dust, smoke, corrosives, flammable gas, vapor or salt mist.
    Humidity:

    1. 24h average RH ≤95%, monthly RH ≤90%;
    2. 24h vapor pressure ≤2.2kPa, monthly ≤1.8kPa.

    Condensation seldom happens here, but may occur with high humidity & sharp temperature shifts. Follow civil engineering standards and equip proper ventilation to prevent insulation damage.

     product Display

    SM6 medium voltage ring main unit view
    SM6 medium voltage ring main unit inside

    Technical Parameters

    Main Electrical Characteristics

    Specification Item 12 kV 24 kV 36 kV
    Rated Voltage (kV) 12 24 36
    Insulation Level
    50Hz / 1min (kV rms) – Earth 42 65* 70
    50Hz / 1min (kV rms) – Interrupt Gap 48 79* 80
    1.2/50μs Lightning Impulse (kV peak) – Earth 95 125 170
    1.2/50μs Lightning Impulse (kV peak) – Interrupt Gap 110 145 195
    Breaking Capacity
    No-load Transformer Breaking Current (A) 16 16 16
    No-load Cable Breaking Current (A) 25 25 50
    Short-time Withstand Current & Duration 25kA 1s
    20kA 3s
    20kA 4s*
    20kA 1s 16kA/1s (630–1250A)
    20kA/1s (630–1250A)
    25kA/1s (1250A)
    5% Rated Load Breaking Current (A) 31.5 31.5 31.5
    Making & Breaking Class E3 E3 E3
    Rated Active Load Breaking Current (A) 630 630 630–1250
    Rated Closed-loop Breaking Current (A) 630 630 630–1250
    Rated Short-circuit Making Current (kA) 50, 63 50 50
    Internal Arc Withstand Capacity 12.5kA/1s or 20kA/1s* 12.5kA/1s or 20kA/1s* 20kA/1s

    *Note: Parameters marked with * are optional configurations, fully compliant with IEC medium voltage switchgear standards.

    General Specifications (12kV / 24kV / 36kV full series)

    Cubicle Model Rated Current / Short-circuit Rating Applicable Voltage
    IM, IMC, IMB, NSM-C 630A 12kV / 24kV / 36kV
    QM, QMC, PM 31.5kA (12kV); 20kA (24kV/36kV) 12kV / 24kV / 36kV
    DM1-A, DM1-D, DM2 25kA (12kV); 20~25kA (36kV) 12kV / 24kV / 36kV

    ● Service continuity category: LSC2A
    ● Partition class: PI
    ● Transfer breaking current: 3 times in accordance with IEC60420 & GB16926

    - 1750A @12kV
    - 1400A @24kV

    Core Structure Zones Introduction

    SM6-3

    1. Switch Compartment: 3-position epoxy encapsulated load switch sealed in SF6 gas tank (sealed pressure system standard). Observation window built-in, gas pressure gauge optional.
    2. Busbar Compartment: All busbars are arranged on the same horizontal plane. The cabinet can be extended laterally to both sides with simple interconnection between units.
    3. Cable Compartment: Cables are connected from the front for easy wiring to switch and earthing switch terminals. For transformer protection configuration, an extra earthing switch is installed below fuses inside this compartment.
    4. Operating Mechanism Compartment: Houses manual operating mechanism to perform closing, opening and earthing operations with clear position indication; electric operating mechanism is optional.
    5. Low Voltage Compartment: Installed with low-voltage fuses, relay protection devices and terminal blocks. An extended low voltage compartment can be added on cabinet top if internal space is insufficient.
    Key Product Feature Summary

    1. Fully sealed SF6 gas tank insulation, stable insulation performance and safe operation
    2. Modular expandable busbar design, flexible for multi-unit ring network configuration
    3. Front cable access layout, convenient on-site wiring and maintenance
    4. Independent compartment layout, mechanical isolation improves operation safety
    5. Customizable accessories: pressure gauge, electric operating device, extended low voltage cabinet

    SF6 Circuit Breaker Cabinet Structure

    SM6-4

    1. Switch Compartment: 3-position epoxy cast switch sealed in SF6 gas tank (sealed pressure system). Observation hole built-in; pressure gauge optional.
    2. Busbar Compartment: Horizontal busbar layout, lateral expandable for easy cabinet connection.
    3. Cable Compartment: Front access for breaker wiring, CT/VT mountable. Two breaker types available:

    - SFset: Self-powered protection with dedicated sensors
    - SF1: Comprehensive relay with standard sensors (auxiliary power required)

    4. Mechanism Compartment: Holds operating unit with position indicator; electric actuator optional.
    5. Low Voltage Compartment: Fits fuses, relays and terminal blocks. Extended low-voltage compartment can be added on top for extra space.