SM6 Modular Air Insulated Medium Voltage Ring Main Unit (RMU)
Normal Operating Conditions
Ambient Temperature: Max 40°C, 24h average ≤35°C, min -25°C
Altitude: 12kV model: ≤2000m; 24kV model: ≤1000m. Derating needed for higher altitudes, contact us.
Sunlight: No direct sunlight exposure.
Environment: No heavy dust, smoke, corrosives, flammable gas, vapor or salt mist.
Humidity:
1. 24h average RH ≤95%, monthly RH ≤90%;
2. 24h vapor pressure ≤2.2kPa, monthly ≤1.8kPa.
Condensation seldom happens here, but may occur with high humidity & sharp temperature shifts. Follow civil engineering standards and equip proper ventilation to prevent insulation damage.
product Display
Technical Parameters
Main Electrical Characteristics
| Specification Item | 12 kV | 24 kV | 36 kV |
| Rated Voltage (kV) | 12 | 24 | 36 |
| Insulation Level | |||
| 50Hz / 1min (kV rms) – Earth | 42 | 65* | 70 |
| 50Hz / 1min (kV rms) – Interrupt Gap | 48 | 79* | 80 |
| 1.2/50μs Lightning Impulse (kV peak) – Earth | 95 | 125 | 170 |
| 1.2/50μs Lightning Impulse (kV peak) – Interrupt Gap | 110 | 145 | 195 |
| Breaking Capacity | |||
| No-load Transformer Breaking Current (A) | 16 | 16 | 16 |
| No-load Cable Breaking Current (A) | 25 | 25 | 50 |
| Short-time Withstand Current & Duration | 25kA 1s 20kA 3s 20kA 4s* |
20kA 1s | 16kA/1s (630–1250A) 20kA/1s (630–1250A) 25kA/1s (1250A) |
| 5% Rated Load Breaking Current (A) | 31.5 | 31.5 | 31.5 |
| Making & Breaking Class | E3 | E3 | E3 |
| Rated Active Load Breaking Current (A) | 630 | 630 | 630–1250 |
| Rated Closed-loop Breaking Current (A) | 630 | 630 | 630–1250 |
| Rated Short-circuit Making Current (kA) | 50, 63 | 50 | 50 |
| Internal Arc Withstand Capacity | 12.5kA/1s or 20kA/1s* | 12.5kA/1s or 20kA/1s* | 20kA/1s |
*Note: Parameters marked with * are optional configurations, fully compliant with IEC medium voltage switchgear standards.
General Specifications (12kV / 24kV / 36kV full series)
| Cubicle Model | Rated Current / Short-circuit Rating | Applicable Voltage |
| IM, IMC, IMB, NSM-C | 630A | 12kV / 24kV / 36kV |
| QM, QMC, PM | 31.5kA (12kV); 20kA (24kV/36kV) | 12kV / 24kV / 36kV |
| DM1-A, DM1-D, DM2 | 25kA (12kV); 20~25kA (36kV) | 12kV / 24kV / 36kV |
● Service continuity category: LSC2A
● Partition class: PI
● Transfer breaking current: 3 times in accordance with IEC60420 & GB16926
- 1750A @12kV
- 1400A @24kV
Core Structure Zones Introduction

1. Switch Compartment: 3-position epoxy encapsulated load switch sealed in SF6 gas tank (sealed pressure system standard). Observation window built-in, gas pressure gauge optional.
2. Busbar Compartment: All busbars are arranged on the same horizontal plane. The cabinet can be extended laterally to both sides with simple interconnection between units.
3. Cable Compartment: Cables are connected from the front for easy wiring to switch and earthing switch terminals. For transformer protection configuration, an extra earthing switch is installed below fuses inside this compartment.
4. Operating Mechanism Compartment: Houses manual operating mechanism to perform closing, opening and earthing operations with clear position indication; electric operating mechanism is optional.
5. Low Voltage Compartment: Installed with low-voltage fuses, relay protection devices and terminal blocks. An extended low voltage compartment can be added on cabinet top if internal space is insufficient.
Key Product Feature Summary
1. Fully sealed SF6 gas tank insulation, stable insulation performance and safe operation
2. Modular expandable busbar design, flexible for multi-unit ring network configuration
3. Front cable access layout, convenient on-site wiring and maintenance
4. Independent compartment layout, mechanical isolation improves operation safety
5. Customizable accessories: pressure gauge, electric operating device, extended low voltage cabinet
SF6 Circuit Breaker Cabinet Structure

1. Switch Compartment: 3-position epoxy cast switch sealed in SF6 gas tank (sealed pressure system). Observation hole built-in; pressure gauge optional.
2. Busbar Compartment: Horizontal busbar layout, lateral expandable for easy cabinet connection.
3. Cable Compartment: Front access for breaker wiring, CT/VT mountable. Two breaker types available:
- SFset: Self-powered protection with dedicated sensors
- SF1: Comprehensive relay with standard sensors (auxiliary power required)
4. Mechanism Compartment: Holds operating unit with position indicator; electric actuator optional.
5. Low Voltage Compartment: Fits fuses, relays and terminal blocks. Extended low-voltage compartment can be added on top for extra space.







Claire
Mr.Fu

Claire