SJKQ1 ATS Automatic Transfer Switch - Reliable Power Solution from China Suppliers & Factory

| 1 | Manufacturer Code |
| 2 | Special Variant Code (ATS) |
| 3 | Frame Size |
| 4 | Circuit Breaker Type: C/DN |
| 5 | Number of Poles: 4P: 4-Pole, 3P: 3-Pole |
| 6 | Controller Type: M: Terminal Type Z: Smart Type |
1. Ambient air temperature: upper limit not exceeding +40°C, lower limit not below -5°C, and 24-hour average not exceeding +35°C.
2. Altitude at installation site: not exceeding 2000m.
3. Relative humidity of the atmosphere: not exceeding 50% at an ambient temperature of +40°C, with higher humidity permissible at lower temperatures; the maximum average relative humidity is 90% when the monthly average minimum temperature of the wettest month is +25°C. Special measures shall be taken to address condensation on the product surface due to humidity fluctuations.
4. Pollution degree: Level III.
Operating environment: free from severe vibration and impact, corrosive or insulation-damaging gases, excessive dust, conductive particles, explosive materials, and strong electromagnetic interference.
| Name | Performance Parameters | ||
| Compliance Standard | GB/T14048.11 | ||
| ATS Class | CB | ||
| Utilization Category | AC-33iB | ||
| Rated Operational Voltage (Ue) | AC220-400V | ||
| Rated Frequency | 50Hz/60Hz | ||
| Rated Current (Ie) | 6A, 10A, 16A, 20A, 25A, 32A, 40A, 63A | ||
| Control Voltage | AC220V | ||
| Nominal Insulation Voltage | AC690V | ||
| Transfer Time | <3s (Factory-Preset (Non-Adjustable)) | ||
| Service Life | Electrical Life | 1500 times | |
| Mechanical Life | 6000 times | ||
| Rated Short-Circuit Making Capacity (Icm) | 7.5KA | ||
| Rated Short-Circuit Breaking Capacity (Icu) | 5KA | ||
| Model | Terminal Type | Smart Type | |
| Installation Type | Integrated Design | ||
| Operation Mode | Auto & Manual Operation | Auto / Manual / Off Mode | |
| Detection Function | Phase-Loss Detection | Undervoltage & Phase-Loss Detection (Main Source) | |
| Conversion Mode | Auto-Recovery | ||
| Fire Linkage Control | None | Fire Alarm Cutoff (DC 12-24V Input) | |
| Display Function | Signal Indication | ||
Dimensions & Installation (Table 3 & Figure 1)

| Model & Size Dimensions | Overall Dimensions | Installation Dimensions | ||||
| L | W | H | L1 | W1 | A d | |
| 4-Pole Switch | 220 | 132 | 120 | 200 | 120 | 4 |
| 3-Pole Switch | 185 | 132 | 120 | 165 | 120 | 4 |