SJK47LE-63 RCCB: Reliable Earth Leakage Protection - China Suppliers & Factory for 230V/400V AC Systems
Type Designation

| 1 | Manufacturer Code |
| 2 | Design Serial Number |
| 3 | With Residual Current Protection (Earth Leakage Protection) |
| 4 | Rated Current Collection (32A, 63A) |
| 5 | Operational Current |
| 6 | Number of Poles |
Product Display
Technical Parameters
Table 1
| Maximum Frame-rated Current (A) | Number of Poles | With Neutral Pole | Rated Current In (A) | Rated Voltage Un (V) | Rated Residual Operating Current I△n (mA) | Rated Residual Non-operating Current I△no (mA) | Breaking Time at I△n (s) | Rated Residual Making & Breaking Capacity I△m (A) | Instantaneous Overcurrent Release Type |
| 32 | 1 | +N | 6 10 16 20 25 |
230 | 30 50 100 300 |
15 25 50 150 |
<0.1 | 2000 | C D |
| 2 | 230 | ||||||||
| 3 | 400 | ||||||||
| 3 | +N | 400 | |||||||
| 4 | 400 | ||||||||
| 63 | 1 | +N | 32 40 50 63 |
230 | |||||
| 2 | 230 | ||||||||
| 3 | 400 | ||||||||
| 3 | +N | 400 | |||||||
| 4 | 400 |
◇Rated Short-Circuit Capacity (Icn), Service Short-Circuit Breaking Capacity (Ics).
Table 2
| Model | Rated Current | Rated Short-Circuit Current (A) | Operating Short-Circuit Breaking Capacity (A) | ||||||
| SJK47LE | 6~63A | 4500 | 4500 | ||||||
| SJK47LEH | 6~63A | 6000 | 6000 | ||||||
◇Overcurrent Protection Characteristics at 30°C~35°C (Ref. Table 3)
Table 3
| No. | Rated Current of Release (A) | Initial State | Test Current | Specified Time | Expected Result | Notes | |||
| 1 | 6~63 | Cold State | 1.13In | t≤1h In≤63A | No Tripping | ||||
| 2 | 6~63 | Immediately after previous test post-test condition | 1.45In | t<1h In≤63A | Tripping | Current Rises Steadily to Specified Value Within 5s | |||
| 3 | In≤32 | Cold State | 2.55In | 1s<t<60s | Tripping | ||||
| In>32 | Cold State | 2.55In | 1s<t<120s | Tripping | |||||
| 4 | 6~63 | Cold State | 5In 10In |
t≤0.1s t<0.1s |
No Tripping Tripping |
C Type | |||
| 10In 14In |
t≤0.1s t<0.1s |
No Tripping Tripping |
D Type | ||||||
◇Wiring: For conductors ≤25mm² (Ref. Table 4) 2N·m — Connection method: Screw-clamp terminals, Torque 2N·m
Table 4
| Rated Current In (A) | Nominal Cross-Sectional Area of Copper Conductor (mm²) |
| 6 | 1 |
| 10 | 1.5 |
| 16、20 | 2.5 |
| 25 | 4 |
| 32 | 6 |
| 40、50 | 10 |
| 63 | 16 |
Outline and Installation Dimensions

Table 5
| 1P+N | 2P | 3P | 3P+N | 4P |
| 18+36 | 36+36 | 54+54 | 54+72 | 72+72 |
Frequently Asked Questions
Q
What is the difference between SJK47LE and SJK47LEH models?
The SJK47LE has a rated short-circuit breaking capacity (Icn) of 4500A, while the SJK47LEH is a higher-performance variant with a rated short-circuit breaking capacity of 6000A. Both cover a rated current range of 6~63A, making SJK47LEH more suitable for installations requiring higher fault current protection.
Q
What residual current (earth leakage) sensitivity options are available?
The SJK47LE-63 series offers four rated residual operating current (I△n) options: 30mA, 50mA, 100mA, and 300mA. The corresponding non-operating currents (I△no) are 15mA, 25mA, 50mA, and 150mA respectively. The breaking time at I△n is less than 0.1 seconds for all options.
Q
What pole configurations are available for this circuit breaker?
The SJK47LE-63 is available in multiple pole configurations: 1P+N (single pole with neutral), 2P, 3P, 3P+N, and 4P. For 32A frame models, the rated voltage is 230V for 1P+N and 2P, and 400V for 3P, 3P+N, and 4P configurations.
Q
What are the C-type and D-type instantaneous overcurrent release characteristics?
C-type breakers trip instantaneously (t<0.1s) at currents above 10In and do not trip at 5In. D-type breakers trip instantaneously (t<0.1s) at currents above 14In and do not trip at 10In. D-type is preferred for loads with high inrush currents such as motors and transformers, while C-type suits general residential and commercial loads.
Q
What copper conductor size should I use with a 63A rated current breaker?
For a 63A rated current, a copper conductor with a nominal cross-sectional area of 16mm² is recommended. The connection method uses screw-clamp terminals with a tightening torque of 2N·m. Always refer to Table 4 for the correct conductor sizing for other current ratings ranging from 6A to 63A.
Q
How much DIN rail space does the SJK47LE-63 occupy?
The installation width depends on the pole configuration. For example, a 1P+N model occupies 18+36mm, a 2P model occupies 36+36mm, a 3P model occupies 54+54mm, a 3P+N model occupies 54+72mm, and a 4P model occupies 72+72mm. This allows accurate panel planning and DIN rail space allocation.