SG(B)10 Type 10kV Series Non-encapsulated Coil Dry Type Transformer
Type & Meaning

| 1 | Three-Phase |
| 2 | Dry Type |
| 3 | Low-Voltage Foil-Wound Coil |
| 4 | Performance Level Code |
| 5 | Rated Capacity (kVA) |
| 6 | Voltage Class (kV) |
Product Features
◇ The carefully designed coil structure and vacuum impregnation process result in low partial discharge for the SG(B)10 transformer, with no cracking or insulation degradation throughout its service life.
◇ The high-voltage side adopts a continuous winding, and the low-voltage side uses foil winding. The whole unit undergoes vacuum impregnation and curing, supported by high-strength ceramic insulators, providing excellent resistance to sudden short-circuit currents.
◇ Flame-retardant, self-extinguishing, non-toxic, and fireproof.
◇ Almost no smoke is generated when the SG(B)10 transformer is burned under high-temperature open flame.
◇ The transformer uses Class H (180°C) insulation, with DuPont NOMEX® paper (Class C) as the main insulation material.
◇ The insulation layer is extremely thin and uniform, enabling strong short-time overload capacity. It can operate at 120% load continuously and 140% load for 3 hours without forced cooling. Thanks to the non-aging and elastic properties of the insulation material, it can immediately carry full load at -50°C.
product Display
Technical Parameters
Technical Parameters of SG(B)10 Series 10kV Non-Encapsulated Coil Dry-Type Transformers
| Rated Capacity (kVA) | Voltage Combination and Tap Range | Connection Symbol | No-Load Loss (W) |
Load Loss(W) 145℃ |
No-Load Current (%) | Short-Circuit Impedance (%) | Main Unit Weight (kg) | Overall Dimensions (mm) | Wheelbase (mm) | |||
| High Voltage (KV) | Tap Changer (%) | Low Voltage (kV) | Length (L)×Width (W)×Height (H) (Without Protective Enclosure) |
Length (L)×Width (W)×Height (H) (With Protective Enclosure) |
||||||||
| 100 | 6 6.3 6.6 10 10.5 11 |
±5 Or ±2×2.5 |
0.4 | Yyn0 Or Dyn11 |
400 | 2160 | 1.7 | 4 | 750 | 1050×600×1000 | 1300×1000×1500 | 550×550 |
| 160 | 560 | 3100 | 1.5 | 950 | 1120×770×1100 | 1400×1100×1500 | 710×660 | |||||
| 200 | 650 | 3970 | 1.4 | 1150 | 1160×770×1150 | 1450×1100×1500 | 710×660 | |||||
| 250 | 750 | 4670 | 1.3 | 13580 | 1220×770×1200 | 1500×1150×1500 | 710×710 | |||||
| 315 | 880 | 5610 | 1.1 | 1600 | 1260×700×1250 | 1550×1150×1550 | 710×710 | |||||
| 400 | 1040 | 6630 | 1.1 | 1750 | 1320×770×1300 | 1600×1150×1600 | 710×710 | |||||
| 500 | 1200 | 7940 | 1.0 | 2050 | 1360×820×1350 | 1650×1200×1650 | 760×710 | |||||
| 630 | 1340 | 9770 | 0.9 | 6 | 2400 | 1420×820×1400 | 1700×1200×1700 | 760×710 | ||||
| 800 | 1690 | 11560 | 0.75 | 2800 | 1500×980×1550 | 1850×1250×1800 | 920×820 | |||||
| 1000 | 1980 | 13340 | 0.65 | 3200 | 1550×980×1600 | 1850×1250×1850 | 920×820 | |||||
| 1250 | 2380 | 15640 | 0.6 | 3800 | 1600×980×1650 | 1900×1250×1900 | 920×820 | |||||
| 1600 | 2730 | 18100 | 0.6 | 4500 | 1700×980×1700 | 2000×1300×2100 | 920×920 | |||||
| 2000 | 3320 | 21250 | 0.5 | 5600 | 1800×980×1800 | 2100×1300×2200 | 920×920 | |||||
| 2500 | 4000 | 24730 | 0.45 | 6300 | 1850×980×1900 | 2100×1300×2300 | 1020×920 | |||||
Notes:The overall dimensions and weight data in the table are for reference only; no prior notice will be given for any changes.
Applicable Standards
◇ GB6450-1986 Dry-Type Power Transformers
◇ GB/T10228-1997 Technical Parameters and Requirements for Dry-Type Power Transformers
◇ GB/T17211-1998 Loading Guide for Dry-Type Power Transformers
◇ GB1094.3-2003 Power Transformers - Part 3: Insulation Levels, Dielectric Tests and Air Clearances for External Insulation
◇ JB/T10088-2004 Sound Levels for 6~500kV Power Transformers
◇ JB/T56009-1998 Product Quality Grading for Dry-Type Power Transformers