Leave Your Message

SC(B)13 Type 10kV Series Resin Insulation Dry Type Power Transformer

The SC(B)13 series 10kV resin insulation dry type power transformer is engineered for exceptional reliability and extended service life in critical applications. Constructed with high-grade epoxy resin and advanced manufacturing processes, it delivers superior fireproof, pollution-free, and moisture-resistant performance. Ideal for high-rise buildings, commercial complexes, and industrial plants, this transformer ensures stable power distribution with low energy loss and minimal maintenance requirements. Its robust design withstands harsh environments, making it a cost-effective solution for modern power systems.

    Type & Meaning

    SC(B)13-3
    1 Three-Phase Transformer
    2 Resin Cast Type
    3 Foil-Wound Coil
    4 Performance Level Code
    5 Rated Capacity (kVA)
    6 Voltage Class (kV)

    Applicable Standards

    - GB6450-1986 Dry-Type Power Transformers
    - GB/T10228-2008 Technical Parameters and Requirements for Dry-Type Power Transformers
    - GB/T17211-1998 Loading Guide for Dry-Type Power Transformers
    - GB1094.3-2003 Power Transformers - Part 3: Insulation Levels, Dielectric Tests and Air Clearances for External Insulation
    - JB/T10088-2004 Sound Levels for 6~500kV Power Transformers
    - JB/T56009-1998 Product Quality Grading for Dry-Type Power Transformers

     product Display

    SC(B)13 Dry Type Power Transformer view
    SC(B)13 Dry Type Power Transformer right

    Technical Parameters

    Technical Parameters of SC(B)13 Series 10kV Epoxy Resin Cast Dry-Type Power Transformers

    Rated Capacity (kVA) Voltage Combination and Tap Range Connection Symbol No-Load Loss (W) Load Loss (W)
    120°
    No-Load Current (%) Short-Circuit Impedance (%) Main Unit Weight (kg) Overall Dimensions (mm) Wheelbase (mm)
    High Voltage (KV) Tap Changer (%) Low Voltage (kV) Length (L)×Width (W)×Height(H)
    (Without Protective Enclosure)
    Length (L)×Width(W)×Height (H)
    (With Protective Enclosure)
    30  6
    6.3
    6.6
    10
    10.5
    11
    ±5
    Or
    ±2×2.5
    0.4  Yyn0
    Or
    Dyn11
    130  710  2.4  380  820×600×820 - 550×550
    50  210  1000  2.1  480  850×600×850 - 550×550
    80  280  1380  1.8  600  950×600×950 - 550×550
    100  300  1570  1.8  750  1040×600×1000 1300×1000×1300 550×550
    125  340  1850  1.6  850  1080×600×1050 1300×1000×1300 550×550
    160  390  2130  1.6  950  1120×770×1100 1400×1000×1400 710×660
    200  440  2530  1.4  1150  1160×770×1150 1450×1100×1450 710×660
    250  520  2760  1.4  1350  1220×770×1200 1500×1150×1500 710×710
    315  640  3470  1.2  1600  1260×770×1250 1550×1150×1550 710×710
    400  710 3990 1.2  1750 1320×770×1300 1600×1150×1600 710×710
    500  800 4880 1.2  2050 1360×820×1350 1650×1200×1650 760×710
    630  900 5960 1.0 2400 1450×820×1410 1800×1250×1800 760×710
    800  1060 6960 1.0  2700 1480×980×1550 1800×1250×1800 920×820
    1000  1240 8130 1.0  3200 1520×980×1600 1850×1250×1850 920×820
    1250  1460 9690 1.0  3700 1600×980×1650 1900×1250×1900 920×820
    1600  1710 11730 1.0 4500 1680×980×1700 1950×1300×1950 920×920
    2000  2170 14450 0.8 4800 1760×980×1800 2000×1300×2100 920×920
    2500  2560 17170 0.8 5300 1900×980×1900 2200×1400×2200 1020×920

    Notes:
    1. For the on-load tap-changing SCZ(B)13 series transformers, only the following data are adjusted: the weight increases by 100kg, the side a (where the on-load tap-changer is installed) increases by 650mm, and the front b increases by 750mm.
    2. The high-voltage side of the on-load tap-changing transformer can provide a voltage regulation range of ±4×2.5%.
    3. The weight and overall dimension data in the table are for reference only; no prior notice will be given for any changes.

    Product Features

    - Safe, fireproof, and pollution-free, it can operate directly at the load center.
    - High mechanical strength, strong short-circuit withstand capability, low partial discharge, good thermal stability, high reliability, and long service life.
    - Low loss, low noise, obvious energy-saving effect, and maintenance-free.
    - Good heat dissipation and strong overload capacity; capacity can be increased with forced air cooling.
    - Good moisture resistance, suitable for operation in high humidity and other harsh environments.
    - Can be equipped with a comprehensive temperature monitoring and protection system. The intelligent signal temperature control system automatically monitors and displays the operating temperature of each three-phase winding on the same screen, automatically starts and stops the fan, and provides alarm and trip functions.
    - Small size, light weight, small footprint, and low installation cost.