S11 Type 35kV/6-10kV Series Power Transformer

The S11 Type 35kV/6-10kV Series Power Transformer complies with the national standards GB 1094 Power Transformers and GB/T 6451 Technical Parameters and Requirements for Three-Phase Oil-Immersed Power Transformers. A series of major reforms in materials, processes, and structures have been adopted, bringing its electrical performance up to the advanced international level of similar products. Featuring high efficiency and low loss, it can save a significant amount of power consumption and operating costs, delivering remarkable social benefits. It is a new product promoted by the state and one of the most popular among users.

    Type & Meaning

    S: Three-Phase Oil-Immersed Transformer
    11: Performance Level Code
    Box 1: Rated Capacity (kVA)
    Box 2: Voltage Class (kV)

    S11-6-10kv-2

    Applicable Standards

    - GB1094.1~2-1996 Power Transformers
    - GB1094.3,5-2003 Power Transformers
    - GB/T6451-2008 Technical Parameters and Requirements for Three-Phase Oil-Immersed Power Transformers

     product Display

    SZ11 10kV Series Power Transformer right
    SZ11 10kV Series Power Transformer side

    Product Features

    - The core is made of high-quality high-permeability silicon steel sheets with fully mitered step-lap joints, which reduces the core's no-load loss and no-load current.
    - The high-voltage winding adopts a continuous type, and the low-voltage winding is either continuous or spiral. The ampere-turn distribution is balanced, and the mechanical strength is high. A new insulation structure is applied to the transformer body, enhancing the short-circuit withstand capability.
    - The oil tank is of barrel or bell-jar type, with corrugated walls for an aesthetic and compact appearance as well as high mechanical strength. Precision-machined flanges are used for key connections to prevent leakage.

    Technical Parameters

    Technical Parameters of S11 Type 35kV Series Distribution Transformer

    Rated
    Capacity
    (kVA)
    Voltage Combination and Tap Range Connection Symbol Loss (kW) Short-Circuit Impedance (%) No-Load Current (%) Weight (kg) Overall Dimensions (mm) Wheelbase (mm)
    High Voltage (kV) Tap Changer (%) Low Voltage (kV) No-Load Load Oil Weight Total Weigh Length (L)×Width (W)×Height(H)
    1000  35
    38.5
    ±5
    ±2×2.5
    6.3
    10.5
    Yd11 1.44  12.15  6.5  1.0  1000  3800  2400×1650×2500 820×820
    1250  1.76  14.67  0.9  1050  4100  2430×1730×2500 820×820
    1600  2.12  17.55  0.8  1100  4700  2470×1750×2530 820×820
    2000  2.72  19.35  0.7  1200  5300  2600×1900×2600 1070×1070
    2500  3.2  20.7  0.6  1350  6200  2650×2100×2700 1070×1070
    3150  3.8  24.3  0.56  1550  7100  2750×2100×2700 1070×1070
    4000  4.52  28.8  0.56  1750  8650  2800×2350×2800 1070×1070
    5000  5.4  33.03  0.48  1950  10000  2900×2500×2900 1070×1070
    6300  6.56  36.9  7.5  0.48  2350  11700  3300×2400×3150 1070×1070
    8000  6.3
    10.5
    YNd11 40.5  0.42  2500  14500  3750×3100×3300 1475×1475
    10000  10.88  47.7  0.42  2850  16500  3400×3200×3400 1475×1475
    12500  12.8  56.7  0.4  3300  18500  3700×3250×3580 1475×1475
    16000  15.2  69.3  0.4  3800  23000  4000×3400×3700 1475×1475
    20000  18  83.7  0.4  4500 27200  4120×3500×3850 1475×1475

    Note: The weight and overall dimension data in the table are for reference only; no prior notice will be given for any changes.