RM6 Fully Enclosed and Fully Insulated Gas-Insulated Ring Network Switchgear
Type & Meaning

| 1 | Model |
| 2 | Rated voltage (kV) |
| 3 | The name of the cabinet type |
| 4 | Cable in and out mode |
Normal Operating Conditions
- Temperature: Maximum 40°C (24h average ≤35°C), minimum -25°C.
- Altitude: 12kV model up to 2000m; 24kV model up to 1000m. For higher altitudes, derating applies – consult us.
- Sunlight: Avoid direct exposure.
- Environment: Free from heavy dust, smoke, corrosive substances, flammable gases, vapor, and salt mist.
- Humidity: 24h average RH ≤95%, monthly average RH ≤90%; 24h vapor pressure ≤2.2kPa, monthly ≤1.8kPa.
While condensation is rare, it may occur under high humidity with sudden temperature changes. Proper ventilation and compliance with civil engineering standards are recommended to prevent insulation damage.
Product Features
- Enhanced Safety: Enclosed design minimizes exposure to live parts, reducing electrical shock risks; built-in protection mechanisms (e.g., arc fault containment) enhance operational safety.
- Reliable Performance: High-quality components ensure stable current control and fault interruption, suitable for continuous operation in harsh industrial environments.
- Flexible Configuration: Modular design allows customization based on voltage levels, load capacities, and application needs (e.g., indoor/outdoor installation).
- Easy Maintenance: Accessible compartments and standardized parts simplify inspection, repair, and component replacement, reducing downtime.
- Smart Integration: Modern switchgear supports remote monitoring and control via digital interfaces, enabling real-time data analysis and predictive maintenance for improved system efficiency.
product Display
Technical Parameters
| Rated voltage | Ur | kV | 12 | 17.5 | 24 | ||||
| Rated frequency | Fr | Hz | 50 or 60 | 50 or 60 | 50 or 60 | ||||
| Insulation level | |||||||||
| Industrial frequency 50Hz/1min |
Phase-to-phase, phase-to-earth | Ud | kV rms | 28 | 38 | 50 | |||
| Across isolating distance | Ud | KV rms | 32 | 45 | 60 | ||||
| Lightning impulse withstand | Phase-to-phase, phase-to-earth | Up | kV peak | 75 | 95 | 125 | |||
| Across isolating distance | Up | kV peak | 85 | 110 | 145 | ||||
| Rated current | Ir | A | 630 | 630 | 400 | 400 | 630 | 630 | |
| Rated current busbars | Ir | A | 630 | 630 | 400 | 400 | 630 | 630 | |
| Rated peak current | lp | kA | 62.5 | 52.5 | 31.25 | 40 | 40 | 50 | |
| Short-time withstand current | It | kA rms | 25 | 21 | 12.5 | 16 | 16 | 20 | |
| tk | S | 1 | 1 or 3 | 1 | 1 | 1 | 1 or 3 | ||
| Breaking capacity | Active load | load | A | 630 | 630 | 400 | 400 | 630 | 630 |
| Earth fault | lef1 | A | 320 | 320 | 320 | 320 | 320 | 320 | |
| Cable charging | Icc | A | 110 | 110 | 110 | 110 | 110 | 110 | |
| Making capacity of switch and earthing switches | Ima | kA peak | 62.5 | 52.5 | 31.25 | 40 | 40 | 50 | |
| Bushing (1) | Type | C | C | B or C | B or C | C | C | ||
| Mechanical endurance | Switch disconrector | M1 | Number of openings | 1000 | 1000 | 1000 | |||
| Earthing switch | M0 | Number of openings | 1000 | 1000 | 1000 | ||||
| Electrical endurance | Switch disconrector | E3 | Number of CO at rated current | 100 | 100 | 100 | |||
| Number of short-circuit making operations | 5 | 5 | 5 | 5 | 5 | 2 | |||
| Earthing switch | E2 | Number of short-circuit making operations | 5 | 5 | 5 | 5 | 5 | 2 | |
(1) No busing for IC function
Monitoring & Protection System
- Testing instrument: Convenient to observe, monitor, the value of current voltage.
- Industry Top Plug: Sealing is stronger, conductive performance good quality reliable safety.
- Three-phase transformer integrated: Three-phase unbalance current outflow and reflux interpolation detection, accurate and reliable detection protection performance.
- Zero sequence current transformer: Using the high accuracy zero sequence current transformer can make a full set of equipment protection function. Safe in operation.