MS116 Low Voltage Motor Protection Circuit Breaker

The ABB MS116-16 is a compact motor protection circuit breaker designed for reliable motor control and protection in industrial applications. It provides comprehensive protection against overload, short-circuit, and phase loss for three-phase motors up to 7.5kW at 400V. With a 16A adjustable current range and Class 10A tripping characteristic, it ensures safe motor starting without nuisance tripping. The unit features a 50kA breaking capacity at 400V, temperature compensation from -25°C to +60°C, and a lockable handle for safety isolation. Its compact 45mm width saves panel space, while modular design allows easy integration with contactors and auxiliary contacts.

    Type and Meaning

    MS116-6.png
    1 Series Number
    MS: Thermal-magnetic trip
    MO: Magnetic-only trip
    2 Rated current, trip class and breaking capacity
    116-32A, Class 10A (10/16/30/50kA)
    132-32A, Class 10A (25/50/100kA)
    450-50A, Class 10A (50kA)
    451-50A, Class 20A (50kA)
    495-100A, Class 10A (50kA)
    496-100A, Class 20A (100kA)
    497-100A, Class 10A (100kA)
    3 Thermal protection setting value

    Product Features

    Model MS116
    Thermal protection and electromagnetic protection Yes
    Electromagnetic protection -
    Phase failure protection Yes
    Switch position… ON/OFF
    Magnetic release indication -
    Lockable handle,no accessories required -
    Isolation function Yes
    Width 45mm
    Rated operating current 0.16...32A
    Current setting range 0.1...32A
    Ambient air temperature -25...+55°C*)

     product Display

    MS116 Low Voltage Motor Protection Circuit Breaker top
    MS116 LV Motor Protection Circuit Breaker view

    Technical Parameters

    Type MS116 MS132 MS165
    Thermal and magnetic protection Yes Yes Yes
    Magnetic protection - - -
    Phase failure protection Yes Yes Yes
    Switch position ON/OFF ON/OFF/TRIP ON/OFF/TRIP
    Magnetic trip indication - Yes Yes
    Lockable handle, no accessories required - Yes Yes
    Isolation function Yes Yes Yes
    Width 45mm 45 mm 55 mm
    Rated operational current (Iₑ) 0.16...32A 0.16..32A 16...65 A
    Current setting range 0.1...32 A 0.1...32 A 10...65A
    Ambient air temperature -25...+55C -25...+60C" -20…+60*C"
    "Compensated

    Rated Short-Circuit Breaking Capacity (for 400/415V)

    Motor Rated Power Thermal Trip Setting Range Type Short-Circuit Breaking Capacity
    Icu Ice
    0.03 kW 0.1…0.16A MS116-0.16 50 kA 50 kA
    0.06 kW 0.16…0.25A MS116-0.25 50kA 50 kA
    0.09 kW 0.25…0.4A MS116-0.4 50kA 50 kA
    0.18 kW 0.4…0.63A MS116-0.63 50kA 50kA
    0.25 kW 0.63…1.0A MS116-1.0 50kA 50kA
    0.55 kW 1.0…1.6A MS116-1.6 50 kA 50 kA
    0.75kW 1.6…2.5A MS116-2.5 50 kA 50 kA
    1.5kW 2.5…4.0A MS116-4.0 50kA 50kA
    2.2 kW 4.0…6.3A MS116-6.3 50kA 50kA
    4.0 kW 6.3...10 A MS116-10 50 kA 50 kA
    5.5 kW 8…12A MS116-12 25 kA 25 kA
    7.5 kW 10…16A MS116-16 16kA 16kA
    7.5 kW 14...20 A
    7.5kW 16…20 A MS116-20 15kA 10 kA
    11 kW 18…25A
    11 kW 20…25A MS116-25 15kA 10 kA
    15 kW 25…32A MS116-32 10 kA 10 kA
    15kW 23...32A
    22 kW 30…42A
    22kW 40...54 A
    30 kW 52…65A
    1)690V

    Outline and Installation Dimension

    MS116-5

    Product Dimensions (mm), inches