Miniature Single-Phase Current-Limiting Protector with LCD Screen 220VAC
Technical Parameters
| Specifications | Unit | Parameters |
| Rated Current | A | 20\32\40\50\63\80 |
| Supply Voltage | VAC | 220 (175~250V) |
| Display | \ | LCD Screen |
| Short Circuit Protection | ms | <150 |
| Overload Protection | \ | Range: 0~100%In adjustable; Delay: 0~60s |
| Overvoltage Protection | \ | Range: 221~300V adjustable; Delay: 0~60s |
| Undervoltage Protection | \ | Range: 100~187V adjustable; Delay: 0~60s |
| Temperature Monitoring | \ | Range: 0~85℃ adjustable; Delay: 0~60s (Optional) |
| Communication | \ | Wired RS485, Wireless LORA, NB, 4G (Optional) |
| Operating Temperature | ℃ | -20~85 |
| Humidity | RH | <95% |
| Dimensions | mm | 105(L)56(W)67(H) |
| Mounting | \ | Standard 35mm DIN rail |
product Display
Outline and Installation Dimension
LCD Display Setting Parameters
| Channel | Alarm Threshold Range | Default Alarm Value | Default Protection Setting | Delay Range | Default Delay |
| Overvoltage | 221–300V | 242V | ON | 0–60s | 3s |
| Undervoltage | 100–219V | 187V | ON | 0–60s | 3s |
| Current | 0–100%In | 100%In | ON | 0–60s | 3s |
| Internal Temperature | 0–85°C | 80°C | ON | 0–60s | 3s |
| Line Temperature | 0–85°C | 80°C | ON | 0–60s | 3s |
| Leakage Current | 30–1000mA | 30mA | ON | 0–60s | 3s |
Other Considerations
● The leakage current transformer is an optional accessory.
● The line temperature sensor is an optional accessory.
● When selecting a current-limiting protector, the rated current set for the protector must match that of the circuit breaker immediately upstream. For example, if the upstream circuit breaker has a rated current of 32A, the current-limiting protector must also be set to 32A. To ensure proper operation, never use a current-limiting protector in a circuit where its rated current does not match that of the upstream circuit breaker.
● The current-limiting protector features a DIN-rail mounting design. It can be installed on a switchgear panel or inside an enclosure with excellent heat dissipation. Ensure the installation location is free of water droplets, corrosive gases, and dust, and pay attention to ambient temperature and ventilation.
● Follow the wiring diagram strictly during installation. To prevent excessive contact resistance from causing local overheating and to avoid malfunctions due to poor connections, ensure all terminal screws on the protector are securely tightened.