MC3000 Series Variable Frequency Drive Cabinet - High-Performance VFD from China Suppliers and Factory
Product Performance
| Item | Parameters |
|---|---|
| Input Voltage | 380V ±20%, unbalance rate <3%, frequency 50/60Hz |
| Output Frequency | 0-500Hz, resolution 0.01Hz |
| Output Voltage | 380V |
| Overload Capacity | 150% rated current for 1 minute; 180% rated current for 3 seconds |
| Modulation Method | Optimized Space Vector Pulse Width Modulation (SVPWM) |
| Control Mode | Sensorless Vector Control (with optimal low-frequency dead-time compensation) |
| Frequency Resolution | 0.01Hz (digital setting); 0.1% × maximum frequency (analog setting) |
| Starting Frequency | 0.4Hz - 20.0Hz |
| Torque Boost | Automatic torque boost; manual torque boost 0.1% - 30.0% |
| Built-in PI | Enables easy configuration of closed-loop control systems |
| Multi-Speed Operation | Realized via built-in PLC or control terminals |
| Operation Command Channel | Control panel setting; control terminal setting; serial communication setting |
| Digital Input Channels | Forward/reverse commands; 8-channel programmable digital input |
| Analog Input Channels | 2-channel analog signal input (4-20mA, 0-10V) |
| Analog Output Channel | Optional 4-20mA or 0-10V analog signal output, supporting multi-parameter outputs such as set frequency and output frequency |
| Digital Pulse Output Channels | 2-channel programmable open-collector output; 2-channel relay output signals; 1-channel 0-20kHz pulse output signal |
| Protection Functions | Overcurrent protection, overvoltage protection, undervoltage protection, overtemperature protection, overload protection, etc. |
Product Display
Technical Parameters
| Model | Rated Capacity (kVA) | Matched Motor Power (kW) | Product Dimensions (mm) |
|---|---|---|---|
| MC3000-4T0004 | 0.4 | 0.4 | 35×24×45 |
| MC3000-4T0007 | 0.75 | 0.75 | 35×24×45 |
| MC3000-4T0015 | 1.5 | 1.5 | 35×24×45 |
| MC3000-4T0022 | 2.2 | 2.2 | 35×24×45 |
| MC3000-4T0037 | 3.7 | 3.7 | 45×30×69 |
| MC3000-4TO055 | 5.5 | 5.5 | 45×30×69 |
| MC3000-4T0075 | 7.5 | 7.5 | 45×30×69 |
| MC3000-4T0110 | 11 | 11 | 42×38×93 |
| MC3000-4T0150 | 15 | 15 | 42×38×93 |
| MC3000-4T0185 | 18.5 | 18.5 | 42×38×93 |
| MC3000-4T0220 | 22 | 22 | 42×38×93 |
| MC3000-4T0300 | 30 | 30 | 60×47×124.5 |
| MC3000-4T0370 | 37 | 37 | 60×47×124.5 |
| MC3000-4T0450 | 45 | 45 | 60×47×124.5 |
| MC3000-4T0550 | 55 | 55 | 60×47×124.5 |
| MC3000-4T0750 | 75 | 75 | 60×47×124.5 |
| MC3000-4T0900 | 90 | 90 | 60×47×124.5 |
Application Scenarios
The MC3000 series variable frequency drive is widely applicable to diverse industrial environments, including petrochemical plants, power substations, construction sites, and manufacturing workshops. It delivers reliable performance in motor speed regulation and energy-saving control for equipment such as pumps, fans, compressors, and processing machinery. Its robust design makes it ideal for both heavy-duty industrial applications and complex power distribution systems, ensuring stable operation in demanding working conditions.
Frequently Asked Questions
What is the input voltage range and frequency requirement for the MC3000 VFD?
The MC3000 series variable frequency drive supports an input voltage of 380V ±20%, with an unbalance rate of less than 3%, and operates at a frequency of 50/60Hz.
What is the overload capacity of the MC3000 series?
The MC3000 series offers high overload durability, handling up to 150% of the rated current for 1 minute and up to 180% of the rated current for 3 seconds.
What control modes and modulation methods are used in this VFD?
It utilizes Sensorless Vector Control (with optimal low-frequency dead-time compensation) and is modulated via Optimized Space Vector Pulse Width Modulation (SVPWM).
What built-in protection functions are integrated into the system?
The drive includes comprehensive safety features such as overcurrent protection, overvoltage protection, undervoltage protection, overtemperature protection, and overload protection.
In which industrial applications can the MC3000 series be deployed?
It is widely used in petrochemical plants, power substations, construction sites, and manufacturing workshops to regulate motor speeds and control equipment like fans, pumps, compressors, and processing machinery.







Claire
Mr.Fu

Claire