KS9 Type 6-10kV Series Mining Oil-immerse Power Transformer

The KS9 series mining transformer is engineered for coal mine underground central substations, shaft bottom yards, and main air intake roadways where gas is present but explosion risk is absent. It is also suitable for relatively humid tunnel environments. Normal operating conditions allow for altitudes up to 1000m and temperatures ranging from -25°C to +40°C. For special conditions exceeding 1000m altitude, the temperature range extends from -45°C to +40°C. The unit withstands up to 95% relative humidity and environments free from severe vibration, with a maximum installation inclination of 35°.

    Type & Meaning

    KS9-2

    K: Mining Type (General Type)
    S: Three-Phase
    9: Performance Level Code
    Box 1: Rated Capacity (kVA)
    Box 2: Voltage Class (kV)

    Product Features

    ● The tank has a robust structure and can withstand a pressure test of one atmosphere. There is no oil conservator on the tank cover. High and low voltage cable junction boxes are welded on both sides of the tank wall for cable connection. The high-voltage winding has rated voltage and ±5% tap voltage, which is adjusted via a tap changer. Voltage adjustment must be performed after cutting off the power supply and removing the weather cover of the tap changer on the tank wall.
    ● The low-voltage side of the transformer can be connected in "Y" configuration for 690V power supply, or reconnected in "△" configuration for 400V power supply. Six porcelain bushings are led out from the secondary terminals in the cable junction box for user modification.
    ● The entire transformer is lifted using lifting lugs welded on the tank wall. A trolley bracket is installed at the bottom of the transformer tank, with mounting holes for installing mine car rollers as required by the mine.

     product Display

    KS9 Type Oil-immerse Power Transformer view
    KS9 Type Oil-immerse Power Transformer left

    Technical Parameters

    Technical Parameters of KS9 Type 6-10kV Series Mining Oil-immerse Power Transformer

    Rated Capacity (kVA) Voltage Combination Connection Symbol No-Load Loss (W) Load Loss (W) Short-Circuit Impedance (%) No-Load
    Current
    (%)
    Weight (kg) Overall Dimensions (mm) Wheelbase (mm)
    High Voltage (KV) Tap Changer (%) Low Voltage (kV) Oil Weight Total Weight Length (L)×Width (W)×Height(H)
    50  6

    6.3

    10
    ±5
    Or

    ±2×2.5
    0.4



    0.69
    Yyn0

    Or

    Yd11
    170  870  4.0  2.0  90  400  1150×750×980 400×200
    80  250  1250  1.8  120  550  1240×770×1010 550×220
    100  290  1500  1.6  130  580  1250×780×1050 550×240
    125  340  1800  1.5  140  650  1280×790×1080 550×240
    160  400  2200  1.4  160  790  1350×820×1120 660×260
    200  480  2600  1.3  190  900  1450×840×1130 660×260
    250  560  3050  1.2  220  1040  1480×920×1200 660×300
    315  670  3650  1.1  250  1200  1500×950×1250 660×300
    400  800  4300  1.0  310  1410  1650×950×1400 660×320
    500  960  5150  1.0  350  1620  1750×980×1500 660×340
    630  1200  6200  4.5  0.9  400  1850  1800×1100×1550 710×360
    800  1400  7500  0.9  600  2200  1900×1200×1700 820×380

    Note: 1. Transformers with a low voltage of 1.2kV can be provided according to user requirements.
    2. The weight and overall dimension data in the table are for reference only; no prior notice will be given for any changes.

    Applicable Standards

    ◇ JB3995-2006        ◇ GB1094.1-1996        ◇ GB1094.2-1996
    ◇ GB/1094.3-2003    ◇ GB/1094.5-2003