Leave Your Message
Products Categories
Featured Products

Intelligent Wireless Automatic Gas Fire Extinguishing Devices - Hot Aerosol Series from China Suppliers & Factory

,

Discover our advanced automatic gas fire extinguishing devices, designed to provide comprehensive protection against electrical fires. Manufactured in China, our intelligent systems monitor wire temperature, ambient temperature, and smoke levels in real-time. With multiple communication options, including RS485, 4G, and Lora, these devices facilitate seamless wireless data uploads to cloud platforms, allowing for remote monitoring and control through a computer or mobile app. Our modular design ensures easy cartridge replacement, making maintenance simple and efficient. Trusted by suppliers and users alike, our automatic gas fire extinguishing devices cover a wide range of protected spaces, including the QRR and YF Hot Aerosol series, offering reliable and cost-effective solutions from our factory.

,

    Type Designation
    QRR MR Type Designation
    Model Communication Method Key Features Ideal For
    QRR□G/S-MR1 Standalone All-in-one unit with integrated detection & extinguishing. No external communication. Basic protection for small, self-contained spaces.
    QRR□G/S-MR2 RS485 Wired Can be integrated into a central fire alarm control panel for centralized monitoring. Buildings or facilities requiring a centralized wired monitoring system.
    QRR□G/S-MR3 LORA Wireless Long-range wireless communication. Flexible installation with low network setup cost. Areas with distributed layouts or where wiring is difficult.
    QRR□G/S-MR4 4G Wireless Connects directly to the cloud platform. Supports remote monitoring and control via mobile app. Multi-site or cross-regional facilities requiring remote, centralized management.
    Product Display
    Product Features

    Simultaneous online detection of wire temperature, ambient temperature, and smoke to prevent electrical fire hazards.

    Equipped with various communication interfaces such as RS485, 4G, and Lora.

    Wireless data upload to the cloud platform enables viewing of on-site data and remote control via computer or mobile app from any location.

    Functions include real-time data collection, historical curves, event recording, and trend analysis.

    Two-segment modular product design allows easy replacement of the extinguishing cartridge after use, enabling repeated use and reducing operational costs.

    Technical Parameters
    Function Configuration QRR □ G/S-MR1 QRR □ G/S-MR2 QRR □ G/S-MR3 QRR □ G/S-MR4
    Communication Method / RS485 LORA / 433MHz 4G
    Dimensions 0.1G/S: 66×45×90mm
    0.3G/S: 66×45×255mm
    0.1G/S: 66×45×170mm
    0.3G/S: 66×45×335mm
    0.1G/S: 66×45×170mm
    0.3G/S: 66×45×335mm
    0.1G/S: 66×45×170mm
    0.3G/S: 66×45×335mm
    Operating Voltage / DC24V
    Agent Quantity 0.1G/S: 100g±2g  |  0.3G/S: 300g±2g
    Protected Space 0.1G/S: ≤1m³  |  0.3G/S: ≤3m³
    Discharge Time ≤14s
    Discharge Delay Time ≤0.5s
    Nozzle Thermal Clearance Temperature at 400mm from nozzle ≤75℃
    Surface Temperature of Enclosure ≤75℃
    Extinguishing Density 100g/m³ ~ 130g/m³
    Agent Service Life 6 Years
    Protected Area Requirements Protected area should be relatively enclosed
    Installation Method 3M adhesive, strong magnetic adsorption, screw fixation
    Operating Environment -40 ~ +85℃  |  <95%RH
    Activation Method Temperature-based activation:
    (when any point of thermal detection line exceeds 170℃)
    Logical activation (temperature exceeds 100℃ and smoke detected simultaneously)
    Remote activation (via host or cloud platform)
    Manual forced start (emergency button, press and hold for 3 seconds)
    Over-temperature activation (when any point of thermal detection line exceeds 170℃)
    Frequently Asked Questions
    Q What communication methods are available for the QRR series?

    The series offers Standalone (MR1), RS485 Wired (MR2), LORA Wireless 433MHz (MR3), and 4G Wireless (MR4) connectivity options to meet diverse installation and networking requirements.

    Q What is the maximum space that one QRR device can protect?

    The 0.1G/S unit (100g agent) covers enclosed spaces up to ≤1m³, while the 0.3G/S model (300g agent) provides coverage for spaces up to ≤3m³.

    Q How does the modular design help lower operational costs?

    The two-segment modular structure allows the extinguishing cartridge to be independently replaced after discharge, avoiding the need to replace the entire electronic detection module.

    Q What triggering methods are supported by the MR2, MR3, and MR4 models?

    They support multi-mode triggering: logical activation (>100℃ simultaneous with smoke detection), remote cloud/host activation, manual forced activation (3-second button press), and thermal detection line activation (>170℃).

    Q What is the service life of the extinguishing agent?

    The extinguishing agent features a maintenance-free service life of up to 6 years under normal operating conditions (-40℃ to +85℃).

    Q Which mounting options are supported for installation?

    The unit supports three flexible mounting options: high-strength 3M industrial adhesive, strong magnetic adsorption, and standard screw fixation.