Leave Your Message

HR6 Industrial Fused Knife Disconnect Switch

The HR6 Industrial Fused Knife Disconnect Switch provides robust circuit protection and isolation for industrial power systems, supporting 4A-630A loads with NT00-NT3 fuse links at 400-600V. This fused disconnect switch integrates high-breaking capacity fuse technology for reliable overload and short-circuit protection, ensuring safe operation in demanding environments. Designed for AC distribution panels, the HR6 switch features a manual knife-disconnect mechanism with visible isolation gaps. Its compatibility with multiple fuse ratings (4-630A) and dual voltage support makes it ideal for motor control centers, machinery, and power distribution cabinets requiring fused protection and maintenance safety.

    Type and Meaning

    HR3-10
    1 Fuse-disconnector
    2 Design code
    3 Rated operational current: 160A,250A,400A,630A
    4 Number of poles: 3-pole
    5 "0" indicates non-contact-signal-device type
    "1" indicates contact-signal-device type

     product Display

    HR3 Knife Switch (1)
    HR3 Knife Switch (2)
    HR3 Knife Switch (3)

    Technical Parameters

    Switch-fuse coordination

    Conventional free-air thermal current (A) Associated fuse-links Rated voltage (A) Fuse element current rating (A)
    160 NT00 400 4,6,10,16,20,25,32,40,50,63,80,100,125,160
    600 4,6,10,16,20,25,32,40,50,63,80,100
    250 NT1 400 80,100,125,160,200,224,250
    600 80,100,125,160,200
    400 NT2 400 125,160,200,224,250,300,355,400
    600 125,160,200,224,250,300,315
    630 NT3 400 315,355,400,425,500,630
    600 315,355,400,425

    Key Technical Parameters of Switches

    Model (number) HR6-160 HR6-250 HR6-400 HR6-630
    Rated insulation voltage (V) 660 660 660 660
    Rated thermal current (A) 100 250 400 630
    Rated operational current (A) 400V 160 250 400 630
    660V 100 200 315 425
    Rated making capacity & Rated breaking capacity (A)
    (1005Ue/time)
    400V,COSΦ=0.35
    AC-23B
    Making 1280 2000 3200 5040
    Breaking 960 1500 2400 3780
    660V,COSΦ=0.65
    AC-22B
    Making 480 750 1200 1890
    Breaking 480 750 1200 1890
    Rated short-circuit breaking current (kA) 50 50 50 50
    Maximum prospective peak current (kA) 100 100 100 100
    Pollution degree 3 3 3 3
    Installation category

    The auxiliary switch has a rated voltage of 400V AC, a conventional heating current of 6A, an utilization category of AC-15,and a rated control capacity of 300VA.

    Outline and Installation Dimension

    HR3-4
    Model Number Overall Dimensions(mm) Mounting Dimensions(mm)
    A B C D E a b c d Φe Φf
    HR6-160/30 134  215  142  245  40  80  198  80  40  Φ6.5 Φ6.5
    HR6-250/30 184  280  162  320  60  120  260  120  60  Φ8.5 Φ8.5
    HR6-400/30 220  300  194  360  72  144  280  144  60  Φ8.5 Φ8.5
    HR6-630/30 244  300  194  360  80  160  280  160  60  Φ8.5 Φ8.5