The HR5 Fused Disconnect Switch delivers reliable circuit protection and isolation for industrial systems, supporting 100-630A loads at AC400-660V with AC-22B/AC-23B utilization categories. This fused disconnect switch features 10le making capacity and 8le breaking capacity under 1.05Ue voltage, ensuring robust performance with 50kA short-circuit breaking capability. Designed for heavy-duty applications, the HR5 switch operates with 0.25-0.65 power factor and handles 3-5 switching cycles per fault condition. Its fused design combines manual control and overload protection, ideal for motor circuits and power distribution panels requiring safe isolation and fault interruption.

    Type and Meaning

    HR3-10
    1 Fuse-disconnector
    2 Design Code
    3 Rated operational current: 100A,200A,400A,630A
    4 Number of poles:2-pole,3-pole
    5 "0" indicates the non-fused signal device type (used with a fuse link equipped with a fuse indicator).
    "1" indicates the fused signal device type (used with a fuse link equipped with a tripping mechanism).

     product Display

    HR3 Knife Switch (1)
    HR3 Knife Switch (2)
    HR3 Knife Switch (3)
    HR3 Knife Switch (3)

    Technical Parameters

    Rated operational voltage Ue(V) Conventional heating voltage Ue(V) Utilization category Rated making and breaking capacity Rated short-circuit breaking capacity
    Make Make Make Break Break Break Operation Root mean square current(KA) COSΦ Switching cycles
    L/le U/Ue COSΦ lc/le Ur/Ue COSΦ Cyclecount
    400  100  AC-23B 10  1.05  0.45  1.05  0.45  50  0.25  Once each
    200  AC-23B 10  1.05  0.35  1.05  0.35  50  0.25  Once each
    400  AC-23B 10  1.05  0.35  1.05  0.35  50  0.25  Once each
    630  AC-23B 10  1.05  0.35  1.05  0.35  50  0.25  Once each
    660  100  AC-22B 1.05  0.65  1.05  0.65  50  0.25  Once each
    200  AC-22B 1.05  0.65  1.05  0.65  50  0.25  Once each
    315  AC-22B 1.05  0.65  1.05  0.65  50  0.25  Once each
    400  AC-22B 1.05  0.65  1.05  0.65  50  0.25  Once each

    Outline and Installation Dimension

    HR3-4
    Model (number) Dimensions (mm)
    a b C d e f (Mounting hole pitch)
    HR5-200/20 203  203  62  193  342  130 
    HR5-200/30 203  203  62  193  342  130 
    HR5-200/31 220  203  62  193  342  130 
    HR5-400/20 226  226  70  210  358  130 
    HR5-400/30 226  226  70  210  358  130 
    HR5-400/31 242  226  70  210  358  130 
    HR5-630/20 272  272  85  224  372  200 
    HR5-630/30 272  272  85  224  372  200 
    HR5-630/31 290  272  85  224  372  200