HR3 Fuse Type Knife Switch for Motor Protection - China Suppliers Factory for Industrial Use and Safety
Type and Meaning
| 1 | Fuse-disconnector |
| 2 | Design Code |
| 3 | Conventional Free-air Thermal Current (A) |
| 4 | Number of Poles (3) |
| 5 |
Operation Method and Maintenance Direction: "1" indicates front side lever transmission mechanism type, front maintenance "2" indicates front central lever transmission mechanism type, rear maintenance "3" indicates side operating handle type, front maintenance "4" indicates front side lever transmission mechanism type without panel, front maintenance |
| 6 | With "BX" indicates rotary operation type; Without "BX" indicates lever operation type (Only for front central type) |
| Rated Heating Current Ith (A) | Rated Operating Current le (A) | AC 400V | |||
| HR3 with Front-side Horizontal Lever-type Operation Mechanism | HR3 with Front-center Horizontal Lever-type Operation Mechanism | HR3 with Front-side Hand-operated Mode | HR3 with Front-panel-front-side Lever-type Operation Mechanism | ||
| 100 | 100 | HR3-100/31 | HR3-100/32 | HR3-100/33 | HR3-100/34 |
| 200 | 200 | HR3-200/31 | HR3-200/32 | HR3-200/33 | HR3-200/34 |
| 400 | 400 | HR3-400/31 | HR3-400/32 | HR3-400/33 | HR3-400/34 |
| 600 | 600 | HR3-600/31 | HR3-600/32 | HR3-600/33 | HR3-600/34 |
| 1000 | 1000 | HR3-1000/32 | HR3-1000/33 | HR3-1000/34 | |
Normal Operating Conditions
- ● The ambient air temperature shall not be higher than +40℃ and not lower than -35℃.
- ● The altitude of the installation site shall not exceed 5000m.
- ● Humidity: When the maximum temperature is +40℃, the relative humidity of the air shall not exceed 50%. At lower temperatures, a higher relative humidity is allowed, such as 90% at 20℃. However, appropriate measures shall be taken due to the influence of temperature changes.
- ● The pollution level of the ambient environment is Grade 3.
- ● The switch shall be installed in a place without severe vibration, and without corrosive gases. Meanwhile, the installation site shall be free of explosive media, and the air in the medium shall be free of gases and dust that can corrode metals and damage insulation.
Product Display
Technical Parameters
| Model | Rated Operating Voltage Us (V) | Rated Insulation Voltage Ui (V) | Rated Heating Current Ith (A) | Rated Operating Current le (A) | Fuse Base Model | Rated Limiting Short-circuit Current (kA) |
| HR3-100 | 400 | 500 | 100 | 100 | RT0-100 | 50 |
| HR3-200 | 200 | 200 | RT0-200 | 50 | ||
| HR3-400 | 400 | 400 | RTO-40 | 50 | ||
| HR3-600 | 600 | 600 | RT0-600 | 50 | ||
| HR3-1000 | 1000 | 1000 | RT0-1000 | 50 |
Outline and Installation Dimension
Outline and Installation Dimensions of HR3/32 Series Switches

| Model | Outline and Installation Dimensions | |||||||||
| A | B | C | D | E | H | J | R | M | φ | |
| HR3-100/32 | 250 | 170 | 210 | 130 | 60 | 190 | 162 | 180 | 8 | 7 |
| HR3-20032 | 270 | 170 | 230 | 130 | 70 | 193 | 176 | 180 | 10 | 7 |
| HR3-400/32 | 290 | 170 | 250 | 130 | 80 | 194 | 194 | 180 | 12 | 7 |
| HR3-600/32 | 320 | 180 | 280 | 130 | 90 | 213 | 218 | 180 | 16 | 7 |
| HR3-100032 | 410 | 310 | 348 | 248 | 115 | 280 | 276 | 230 | 12 | 8.5 |
Outline and Installation Dimensions of HR3/33 Series Switches

| Model | Outline and Installation Dimensions | ||||||||||
| A | B | C | D | E | F | G | H | J | M | Φ | |
| HR3-100/33 | 250 | 200 | 210 | 170 | 60 | 77 | 68 | 190 | 162 | 8 | 7 |
| HR3-200/33 | 270 | 205 | 230 | 170 | 70 | 77 | 60 | 193 | 176 | 10 | 7 |
| HR3-400/33 | 290 | 290 | 250 | 170 | 80 | 77 | 55 | 194 | 194 | 12 | 7 |
| HR3-600/33 | 320 | 320 | 280 | 170 | 90 | 94 | 50 | 214 | 218 | 16 | 7 |
| Note: Dimension marked with F is the size when the operating handle is in the maximum open position. | |||||||||||
Outline and Installation Dimensions of HR3/34 Series Switches

| Model | Outline and Installation Dimensions | |||||||||||
| A | B | C | D | E | F | G | H | R | J | M | Φ | |
| HR3-100/34 | 250 | 200 | 210 | 170 | 60 | 80 | 43 | 250 | 180 | 162 | 8 | 7 |
| HR3-200/34 | 270 | 205 | 230 | 170 | 70 | 80 | 53 | 250 | 180 | 176 | 10 | 7 |
| HR3-400/34 | 290 | 225 | 250 | 170 | 80 | 80 | 43 | 250 | 180 | 194 | 12 | 7 |
| HR3-600/34 | 320 | 265 | 280 | 170 | 90 | 95 | 43 | 250 | 180 | 218 | 16 | 7 |
| HR3-1000/34 | 410 | 352 | 348 | 248 | 115 | 115 | 65 | 350 | 230 | 276 | 12 | 8.5 |
| Note: Dimension marked with F is the size when the operating handle is in the maximum open position. | ||||||||||||
Frequently Asked Questions
Q
What is the HR3 fuse-disconnector used for?
The HR3 fuse-disconnector is designed for use in AC 400V power distribution systems. It provides both circuit isolation and overcurrent protection by integrating a fuse base, making it suitable for industrial power distribution panels and switchgear cabinets.
Q
What current ratings are available for the HR3 series?
The HR3 series is available in five rated heating current and rated operating current levels: 100A, 200A, 400A, 600A, and 1000A, covering a wide range of industrial load requirements.
Q
What are the different operation types for the HR3 switch?
The HR3 series offers four operation methods: front side lever transmission mechanism (type 1, front maintenance), front central lever transmission mechanism (type 2, rear maintenance), side operating handle (type 3, front maintenance), and front side lever mechanism without panel (type 4, front maintenance). Additionally, a rotary operation type (BX) is available for front central models.
Q
What are the installation environment requirements for the HR3 switch?
The HR3 switch should be installed in environments where the ambient temperature is between -35℃ and +40℃, altitude does not exceed 5000m, relative humidity is no more than 50% at 40℃, and the pollution level is Grade 3. The installation site must be free from severe vibration, corrosive gases, explosive media, and dust that could damage insulation or corrode metal parts.
Q
What is the rated limiting short-circuit current of the HR3 series?
All models in the HR3 series (HR3-100, HR3-200, HR3-400, HR3-600, and HR3-1000) have a rated limiting short-circuit current of 50kA at AC 400V, providing reliable protection against high fault currents in industrial applications.
Q
How do I select the correct HR3 model for my application?
To select the correct HR3 model, consider the required rated operating current (100A–1000A), the preferred operation and maintenance method (types 1–4), and whether rotary (BX) or lever operation is needed. Refer to the model designation table: for example, HR3-400/33 indicates a 400A rated current with side operating handle type and front maintenance configuration.