High-Voltage Vacuum Load Switch FZ(R)N21C-40.5D for Renewable Energy | China Suppliers & Factory

The FZ(R)N21C-40.5D is a high-voltage indoor vacuum load switch specifically engineered for 40.5kV applications in wind and photovoltaic power systems. As a leading product from a reputable factory in China, this switch incorporates advanced vacuum arc-extinguishing technology within a compact design, making it an ideal choice for energy suppliers seeking reliability and efficiency. With rated currents ranging from 630A to 1250A and a short-time withstand capacity of 25kA, this modular switch ensures comprehensive protection, supported by optional current-limiting fuses. Its durable construction is built to withstand challenging environmental conditions, including cold, humid, and polluted settings. Perfect for substations and distribution networks, the FZ(R)N21C-40.5D guarantees safe operation with minimal maintenance, making it the go-to solution for renewable energy applications in the global market

    Type & Meaning
    CJX2-D-4
    1 Vacuum load switch
    2 R: With fuse base
    3 Indoor
    4 Design serial number
    5 Rated voltage (kV)
    6 D: With grounding switch
    7 T: Spring operating mechanism
    8 Maximum rated current of fuse (A)
    9 Rated short-circuit breaking current of fuse (kA)
    Normal Service Conditions

    a) Ambient temperature: maximum +65°C, minimum -40°C;
    b) Ambient humidity:
       Daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%;
       Daily average vapor pressure ≤ 2.2 kPa, monthly average vapor pressure ≤ 1.8 kPa;
    c) Altitude: not exceeding 4000 meters;
    d) Seismic intensity: not exceeding 8 degrees;
    e) Installation site free from fire and explosion hazards;
    f) Ambient air not significantly polluted by dust, corrosive or flammable gases, vapors, or salt mist.

    Note: Requirements beyond normal service conditions shall be negotiated with the manufacturer.

    Product Display
    cjx2-d-ac-contactor-right-view
    cjx2-d-ac-contactor-top-view
    Technical Parameters

    4.1 The main technical parameters of the load switch are shown in Table 1.

    No. Parameter Unit Load Switch Combination Apparatus
    1 Rated Frequency Hz 50
    2 Rated Voltage kV 40.5
    3 Power Frequency Withstand Voltage (1 min) Phase & Earth / Vacuum Gap kV 95 Note *
    Isolation Gap kV 118 Note *
    4 Rated Lightning Impulse Withstand Voltage (Peak) Phase & Earth / Vacuum Gap kV 185 Note *
    Isolation Gap kV 215 Note *
    5 Auxiliary & Control Circuit Power Frequency Withstand Voltage (1 min) kV 2
    6 Rated Current A 630, 1250 Max. Rated Current of Fuse: 63, 80, 100
    7 Rated Short-Circuit Breaking Current kA 31.5, 40, 50
    8 Rated Active Load Breaking Current A 630, 1250
    9 Rated No-Load Transformer Breaking Current 63, 125
    10 Rated Closed-Loop Breaking Current A 630, 1250
    11 Rated Short-Time Withstand Current (4s) kA 25
    12 Rated Peak Withstand Current kA 63
    13 Rated Short-Circuit Making Current (Peak) kA 63
    14 Rated Transfer Current A 2000
    15 Rated Cable Charging Current A 21
    16 Rated Line Charging Current A 2.1
    17 Rated Earth Fault Breaking Current A 100
    18 Mechanical Life (Load Switch / Disconnector / Earthing Switch) times 10000 / 2000 / 2000
    19 Rated Operating Voltage V ≈ 220 / 110
    20 Permissible Cumulative Wear of Moving & Fixed Contacts mm 3
    21 Contact Gap mm 18 ± 1
    22 Over-Travel mm 4 ± 1
    23 Contact Bounce Time at Closing ms ≤ 5
    24 Three-Phase Closing/Opening Asynchronism ms ≤ 2
    25 Average Opening Speed m/s 1.5 ± 0.3
    26 Average Closing Speed m/s 0.8 ± 0.2
    27 Main Circuit Resistance (incl. Isolator) μΩ ≤ 200 ≤ 300 (excluding fuse)
    28 Contact Pressure N 1600 ± 200
    29 Phase-to-Phase Center Distance mm 440 ± 3 (High-Altitude Type: 500 ± 3)

    Note *: Relevant parameters are adjusted according to altitude.

    Structure and Principle
    Basic Structure

    This three-phase load switch/combination unit consists of a frame, solid-insulated poles, a spring operating mechanism, isolation/earthing blades, sensors, and transmission parts. The isolating blades and vacuum interrupters are mounted on the frame. The earthing blades are at the bottom, and the operating mechanism (manual/electrical) is on the left side.

    Working Principle

    Vacuum Switch: Uses a spring mechanism for closing and a solenoid/manual knob for opening. AC/DC power is supported. Status is visible through a window.
    Isolation/Earthing Blades: Mechanically interlocked; vacuum switch must be open first. Operated via handle with clear status indication.
    Fuse Trip: Uses striker-type fuses. Any phase fuse operation triggers a mechanical release to open the vacuum interrupter reliably (1–3J trip energy).

    Outline and Installation Dimension
    CJX2-D-4
    Frequently Asked Questions
    What is the rated voltage of the FZ-R-N21C-40.5D vacuum load switch?
    The rated voltage of this vacuum load switch is 40.5 kV, making it suitable for medium-voltage indoor power distribution applications.
    What does the "R" suffix in the product model name indicate?
    "R" in the model designation indicates that the unit is equipped with a fuse base, forming a combination apparatus (load switch + fuse) for enhanced short-circuit protection.
    What are the altitude and temperature limitations for normal service conditions?
    The switch is rated for altitudes not exceeding 4,000 meters, with an ambient temperature range of -40°C to +65°C. For installations at higher altitudes, electrical parameters such as withstand voltage are adjusted accordingly.
    How does the fuse trip mechanism work in the combination apparatus?
    The combination unit uses striker-type fuses. When any phase fuse operates, its striker triggers a mechanical release that reliably opens the vacuum interrupter. The required trip energy is between 1 and 3 joules.
    What is the mechanical life expectancy of the load switch and earthing switch?
    The load switch is rated for 10,000 mechanical operations, while the disconnector and earthing switch are each rated for 2,000 operations under standard service conditions.
    Is this vacuum load switch suitable for high-altitude installations?
    Yes, a high-altitude version is available. For high-altitude installations, the phase-to-phase center distance increases to 500 ± 3 mm (standard is 440 ± 3 mm), and withstand voltage parameters are adjusted to meet relevant standards. Please consult the manufacturer for specific requirements.