HH15(QSA) Knife Melt Isolation Switch with Fuse - Reliable Circuit Protection from China Suppliers and Factory
Type Designation

| 1 | Isolator-fuse combination |
| 2 | Design serial number |
| 3 | Conventional heating current (A) |
| 4 | Number of poles: 2-pole, 3-pole, 4-pole |
| 5 | Indicates the number of auxiliary contacts: 0 - No auxiliary contacts; 1 - With 1 pair of auxiliary contacts; 2 - With 2 pairs of auxiliary contacts. |
| 6 | "QP" indicates a structure without a fuse and with parallel contacts "QA" indicates a structure without a fuse and with series contacts. "QSA or no letter" indicates a structure with a fuse and series contacts. |
| 7 | Type Code Explanation, Single-Throw, S: Double-Throw |
Technical Parameters
| Specification (s) | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | |
| Main pole number | 3, 4, 3+N | 3 | ||||||||
| Rated insulation voltage (V) | Ue=400 time, Uj=660; Ue=660 time, Uj=1000. | |||||||||
| Rated working voltage (V) | AC=380, 660 | |||||||||
| Rated enclosed heating current (A) | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | |
| Rated operating current (A) | 400VAC-23B | 63 | 125 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 |
| 660VAV-23B | 63 | 100 | 160 | 250 | 315 | 425 | 500 | 630 | 800 | |
| Rated limited short-circuit current 380VY/H (kA) | 100 | 50 | ||||||||
| Rated limited short-circuit current 660V (kA) | 50 | |||||||||
| Mechanical life (times) | 15000 | 15000 | 12000 | 12000 | 12000 | 3000 | 500 | 500 | 500 | |
| Electrical life (times) | 1000 | 1000 | 300 | 300 | 300 | 200 | 100 | 100 | 100 | |
| Fuse rated current (A) 400V/1660V time | 63/63 | 125/100 | 160/160 | 250/250 | 400/315 | 630/425 | 800/500 | 1000/630 | 1250/800 | |
| Model of fuse tube with knife-type contacts | RDT16-00 (NT00) | RDT16-1 (NT1) | RDT16-2 (NT2) | RDT16-3 (NT3) | RS0 | |||||
| Operating torque (Nm) | 7.5 | 16 | 30 | 40 | ||||||
| Rated heating current of auxiliary contact ITH380V/AC-11 (A) | 5 | |||||||||
Product Display
Outline and Installation Dimensions
Outline and installation dimensions of HH15(QSA) series isolating switch-fuse combinations

| Model specifications | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15-63 | 12 | 6 | 100 | M5 | 2 | 39.5 | 72 | 38.5 | 9 | 199-250 | 250-301 | 301-385 | 180-199 |
| HH15-125 | 15 | 7.5 | 116 | M6 | 3 | 38.5 | 70 | 40.5 | 10 | 199-250 | 250-301 | 301-385 | 180-199 |

| Model specifications | A | B | C | D | E | F | G | H | I | L | L1 | L2 | O |
| HH15-160 | 20 | 10 | 146 | M8 | 4 | 44 | 107 | 65 | 46 | 226-284 | 284-342 | 342-400 | 120 |
| HH15-250 | 25 | 12.5 | 160 | M10 | 4 | 40 | 107 | 65 | 43.5 | 226-284 | 284-342 | 342-400 | 160 |
| HH15-400 | 25 | 12.5 | 160 | M10 | 6 | 38 | 107 | 65 | 43.5 | 226-284 | 284-342 | 342-400 | 160 |

| Model specifications | A | B | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15-630 | 40 | 20 | 270 | M12 | 6 | 33 | B7 | 87 | 60 | 300-355 | 295-330 | 300-400 | 400-500 |

| Model specifications | A | B1 | C | D | E | F | G | H | I | L | L1 | L2 | L3 |
| HH15-800/1000 | 50 | 18 | 340 | M12 | 1 | 33 | 87 | 87 | 60 | 300-355 | 295-330 | 330-400 | 400-500 |
| HH15(QSA)-800/3 Single Hole | 50 | 18 | 340 | M12 | 1 | 33 | 87 | 87 | 38 | 300-355 | 295-330 | 330-400 | 400-500 |

| Model specifications | A | B | C | D | E | F | G | H | I | L | L1 | L2 | M | N | O |
| HH15-1250 | 70 | 17 | 370 | M10 | 8 | 50 | 120 | 120 | 80 | 395-430 | 495-530 | 560-595 | 400 | 330 | 153 |
Frequently Asked Questions
What is the HH15(QSA) series isolating switch-fuse combination used for?
The HH15(QSA) series is a fuse isolation switch designed to provide both isolation and overcurrent protection in AC power distribution systems. It is widely used in industrial switchgear panels operating at voltages up to 660V AC.
What rated current ranges are available for the HH15(QSA) series?
The HH15(QSA) series is available in a wide range of conventional heating currents including 63A, 125A, 160A, 250A, 400A, 630A, 800A, 1000A, and 1250A, making it suitable for various load requirements.
What is the difference between QP, QA, and QSA structure designations?
"QP" indicates a structure without a fuse and with parallel contacts; "QA" indicates a structure without a fuse and with series contacts; "QSA or no letter" indicates a structure with a fuse and series contacts.
What pole configurations are supported by the HH15(QSA) series?
The HH15(QSA) series supports 3-pole, 4-pole, and 3+N pole configurations for models up to 630A. For higher ratings (800A–1250A), only 3-pole configurations are available.
What type of fuse tubes are compatible with the HH15(QSA) series?
Compatible fuse tubes include RDT16-00 (NT00) for 63A–160A models, RDT16-1 (NT1) for 250A, RDT16-2 (NT2) for 400A, RDT16-3 (NT3) for 630A–800A models, and RS0 type fuses for 1000A and 1250A models.
What is the mechanical and electrical lifespan of the HH15(QSA) switch?
Mechanical life ranges from 500 to 15,000 operations depending on the current rating — smaller models (63A–125A) achieve up to 15,000 operations, while larger models (800A–1250A) are rated at 500 operations. Electrical life ranges from 100 to 1,000 operations accordingly.