HGL Load Isolation Switch 63A-3150A - Reliable China Suppliers & Factory for Industrial Power Solutions
Type Designation
| 1 | Rear operation (omit if not required). |
| 2 | Rear wiring (omit for front wiring). |
| 3 | Auxiliary contact function code (see table), omit if not required. |
| 4 | Direct viewing of contact window (omit if not required). |
| 5 | External operation (omit for internal operation). |
| 6 | Number of poles: 3-pole, 4-pole (3-pole + switchable neutral pole). |
| 7 | Rated current |
| 8 | C Side Operation - Disconnector, Z Transfer - Disconnector |
| 9 | Disconnector designation |
| 1NO+1NC | 11 NO+NC |
| 2NO+2NC | 22 2NO+2NC |
Selection example: Disconnector with switchable neutral pole, rated current 630A, externally operated (Model: HGLZ-630A/4J)
Technical Parameters
| Conventional Free-air Thermal Current Ith (A) | 63A | 100A | 160A | 250A | 400A | 630A | 1000A | 1250A | 1600A | 2000A | 2500A | 3150A | ||
| Rated Insulation Voltage (Ui) | 750V | 800V | 1000V | |||||||||||
| Dielectric Strength | 3000V | 3500V | ||||||||||||
| Rated Impulse Withstand Voltage (Uimp) | 6kV | 8kV | 12kV | |||||||||||
| Rated Operational Voltage (Ue) | AC400、600V | |||||||||||||
| Rated Frequency | 50Hz | |||||||||||||
| Utilization Category | AC-21、22、23 | |||||||||||||
| Rated Operational Current Ie(A) | AC400V | AC-21 | 63 | 63 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3150 |
| AC-22 | 63 | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3150 | ||
| AC-23 | 50 | 80 | 160 | 250 | 400 | 630 | 800 | 1000 | 1250 | 1250 | 2000 | 2500 | ||
| AC660V | AC-21 | 63 | 100 | 160 | 250 | 400 | 630 | 1000 | 1250 | 1600 | 2000 | 2500 | 3150 | |
| AC-22 | 63 | 80 | 100 | 200 | 315 | 400 | 630 | 630 | 800 | 1000 | 1000 | 1250 | ||
| AC-23 | 40 | 63 | 63 | 125 | 200 | 250 | 250 | 400 | 500 | / | / | / | ||
| Rated Making Capacity (A) | 10le | |||||||||||||
| Rated Breaking Capacity (A) | 8le | |||||||||||||
| Rated Short-circuit Making Capacity Icm(kA) | 1.7 | 1.7 | 12 | 17 | 30 | 40 | 70 | 70 | ||||||
| Rated Short-time Withstand Current Is Icw(kA) | 3 | 3 | 10 | 12 | 20 | 25 | 50 | 50 | ||||||
| Mechanical Endurance (operations) | 5000 | 5000 | 5000 | 3000 | 2000 | 1000 | ||||||||
| Electrical Endurance (operations) | 1000 | 1000 | 1000 | 600 | 300 | / | ||||||||
| Operating Torque (N·m) | 3.5 | 3.5 | 6.5 | 10 | 15 | 15 | 27 | 60 | ||||||
| Weight (kg) (excluding handle) | 3-Pole | 0.32 | 0.39 | 0.88 | 1.6 | 3.8 | 4.2 | 10.5 | 10.5 | 16 | 31 | 31 | 42 | |
| 4-Pole | 0.34 | 0.41 | 1.1 | 2 | 4.6 | 5 | 13 | 13 | 20 | 40 | 40 | 49 | ||
Product Display
Outline and Installation Dimensions
HGL-63~100A Series Disconnector Outline and Installation Dimensions
HGL-125~630A Series Disconnector Outline and Installation Dimensions
| Specification | Mounting Plate Dimensions | ||||
| L | M | Z | W | Q | |
| HGL-125A | 55 | 5.5 | 85 | 190 | 218 |
| HGL-160A | 55 | 5.5 | 85 | 190 | 218 |
| HGL-200A | 55 | 5.5 | 85 | 190 | 218 |
| HGL-250A | 55 | 5.5 | 85 | 190 | 218 |
| HGL-315A | 60 | 6.5 | 130 | 240 | 270 |
| HGL-400A | 60 | 6.5 | 130 | 240 | 270 |
| HGL-500A | 60 | 6.5 | 130 | 240 | 270 |
| HGL-630A | 60 | 6.5 | 130 | 240 | 270 |
| Specification | Outline and Mounting Dimensions | ||||||||||||||||||
| A | B | C | D | D1 | E | AL | J | K | N | P | R | S | T | U | AX | Y | F | H | |
| HGL-125A/3 | 140 | 135 | 120 | 27 | 93 | 73 | 5.5 | 120 | 65 | 85 | 36 | 20 | 25 | 3.5 | 115 | 9 | 24 | 49 | 10 |
| HGL-125A/4 | 170 | 135 | 120 | 27 | 93 | 73 | 5.5 | 150 | 65 | 85 | 36 | 20 | 25 | 3.5 | 115 | 9 | 24 | 49 | 10 |
| HGL-160A/3 | 140 | 135 | 120 | 27 | 93 | 73 | 5.5 | 120 | 65 | 85 | 36 | 20 | 25 | 3.5 | 115 | 9 | 24 | 49 | 10 |
| HGL-160A/4 | 170 | 135 | 120 | 27 | 93 | 73 | 5.5 | 150 | 65 | 85 | 36 | 20 | 25 | 3.5 | 115 | 9 | 24 | 49 | 10 |
| HGL-200A/3 | 180 | 165 | 140 | 35 | 103 | 86 | 7 | 160 | 90 | 115 | 50 | 25 | 28 | 3.5 | 140 | 11 | 25 | 79 | 15 |
| HGL-200A/4 | 230 | 165 | 145 | 35 | 103 | 86 | 7 | 210 | 90 | 115 | 50 | 25 | 28 | 3.5 | 140 | 11 | 27 | 79 | 15 |
| HGL-250A/3 | 180 | 165 | 140 | 35 | 103 | 86 | 7 | 160 | 90 | 115 | 50 | 25 | 28 | 3.5 | 140 | 11 | 25 | 79 | 15 |
| HGL-250A/4 | 230 | 165 | 145 | 35 | 103 | 86 | 7 | 210 | 90 | 115 | 50 | 25 | 28 | 3.5 | 140 | 11 | 27 | 79 | 15 |
| HGL-315A/3 | 230 | 234 | 170 | 50 | 134 | 116 | 7 | 210 | 140 | 145 | 65 | 32 | 37 | 5 | 205 | 11 | 37 | 94 | 20 |
| HGL-315A/4 | 290 | 234 | 170 | 50 | 134 | 116 | 7 | 270 | 140 | 145 | 65 | 32 | 37 | 5 | 205 | 11 | 37 | 94 | 20 |
| HGL-400A/3 | 230 | 234 | 170 | 50 | 134 | 116 | 7 | 210 | 140 | 145 | 65 | 32 | 37 | 5 | 205 | 11 | 37 | 94 | 20 |
| HGL-400A/4 | 290 | 234 | 170 | 50 | 134 | 116 | 7 | 270 | 140 | 145 | 65 | 32 | 37 | 5 | 205 | 11 | 37 | 94 | 20 |
| HGL-500A/3 | 230 | 250 | 170 | 50 | 134 | 116 | 7 | 210 | 140 | 145 | 65 | 40 | 45 | 6 | 215 | 12.5 | 38 | 94 | 20 |
| HGL-500A/4 | 290 | 250 | 170 | 50 | 134 | 116 | 7 | 270 | 140 | 145 | 65 | 40 | 45 | 6 | 215 | 12.5 | 38 | 94 | 20 |
| HGL-630A/3 | 230 | 250 | 170 | 50 | 134 | 116 | 7 | 210 | 140 | 145 | 65 | 40 | 45 | 6 | 215 | 12.5 | 38 | 94 | 20 |
| HGL-630A/4 | 290 | 250 | 170 | 50 | 134 | 116 | 7 | 270 | 140 | 145 | 65 | 40 | 45 | 6 | 215 | 12.5 | 38 | 94 | 20 |
HGL-1000~3150A Series Disconnector Outline and Installation Dimensions
Terminal Blocks Technical Reference
| Specifications | Overall Dimensions and Installation Dimensions | ||||||||
| A | B | J | K | N | R | S | T | Y | |
| HGL-1000A/3 | 378 | 328 | 352 | 175 | 185.5 | 60 | 64 | 8 | 48 |
| HGL-1000A/4 | 492 | 328 | 467 | 175 | 246 | 60 | 64 | 8 | 48 |
| HGL-1250A/3 | 378 | 336 | 352 | 175 | 185.5 | 80 | 68 | 8 | 48 |
| HGL-1250A/4 | 492 | 336 | 467 | 175 | 246 | 80 | 68 | 8 | 48 |
| HGL-1600A/3 | 378 | 336 | 352 | 175 | 185.5 | 80 | 68 | 10 | 49 |
| HGL-1600A/4 | 492 | 336 | 467 | 175 | 246 | 80 | 68 | 10 | 49 |
| HGL-2000A/3 | 379 | 423 | 352 | 220 | 185.5 | 80 | 111.5 | 10 | 210.5 |
| HGL-2000A/4 | 492 | 423 | 467 | 220 | 246 | 80 | 111.5 | 10 | 210.5 |
| HGL-2500A/3 | 378 | 433 | 352 | 220 | 185.5 | 80 | 116.5 | 15 | 215.5 |
| HGL-2500A/4 | 492 | 433 | 467 | 220 | 246 | 80 | 116.5 | 15 | 215.5 |
| HGL-3150A/3 | 378 | 443 | 352 | 220 | 185.5 | 80 | 121.5 | 20 | 220.5 |
| HGL-3150A/4 | 492 | 443 | 467 | 220 | 246 | 80 | 121.5 | 20 | 220.5 |
Frequently Asked Questions
QWhat is the difference between HGLC and HGLZ type disconnectors?
The HGLC is a C-side operation disconnector designed for standard side-access switching, while the HGLZ is a transfer disconnector suited for applications requiring a switchable neutral pole and transfer between supply sources. The model suffix (C or Z) in the type designation indicates which variant is being specified.
QWhat current ratings are available for the HGL series disconnector?
The HGL series covers a wide range of rated currents: 63A, 100A, 160A, 250A, 400A, 630A, 1000A, 1250A, 1600A, 2000A, 2500A, and 3150A, making it suitable for both light commercial and heavy industrial power distribution applications.
QWhat is the rated insulation voltage and impulse withstand voltage of the HGL disconnector?
For 63A and 100A models, the rated insulation voltage (Ui) is 750V with an impulse withstand voltage (Uimp) of 6kV. For 160A models, Ui is 800V and Uimp is 8kV. For 250A and above, Ui reaches 1000V and Uimp is 12kV, ensuring compatibility with high-voltage distribution environments.
QCan the HGL disconnector be operated externally or remotely?
Yes. The HGL series supports both internal and external operation configurations. When external operation is required, it is specified in the type designation (position 5). Rear operation is also available as an option, indicated at position 1 of the type code. This flexibility allows integration into various panel and switchgear layouts.
QWhat auxiliary contact configurations are supported?
The HGL disconnector supports two auxiliary contact configurations: 1NO+1NC (code: 11) and 2NO+2NC (code: 22). The auxiliary contact function code is specified at position 3 of the type designation and can be omitted if auxiliary contacts are not required for the application.
QHow do I select the correct HGL disconnector model for my application?
Model selection is based on the required rated current, number of poles (3-pole or 4-pole with switchable neutral), operation mode (internal or external), wiring direction (front or rear), and auxiliary contact requirements. For example, a 630A 4-pole externally operated transfer disconnector would be specified as: HGLZ-630A/4J. Refer to the type designation table for a complete breakdown of each code position.







Claire
Mr.Fu

Claire