GN30-12(D) Rotary Indoor High-Voltage Disconnector

The GN30-12 series rotary indoor high-voltage disconnector is a new type of rotary contact-blade disconnector. Its main structure consists of two sets of insulators and contacts fixed on the upper and lower planes of a common three-phase base frame, with opening and closing achieved by rotating the contact blade. The GN30-12D variant, based on the GN30-12, adds an earthing switch to meet diverse power system needs. Compact and space-saving, it offers strong insulation performance and easy installation/adjustment. Compliant with GB1985-2004 "AC High-Voltage Disconnectors and Earthing Switches", it is suitable for indoor 12kV, 50Hz power systems to switch circuits under energized, no-load conditions, and can be used with high-voltage switchgear or independently.

    Type & Meaning

    CJX2-D-4
    1 Disconnector
    2 Indoor type
    3 Design serial number
    4 Rated voltage
    5 With earthing device
    6 Rated current
    7 Rated short-time withstand current (4s)

    Normal Service Conditions

    ● Altitude: ≤ 1000 m.
    ● Ambient air temperature: upper limit +40℃; lower limit -10℃.
    ● Relative humidity: daily average ≤ 95%; monthly average ≤ 90%.
    ● Seismic intensity: ≤ Grade 8.
    ● Locations free from severe dust, chemical corrosion, and explosive substances.
    ● Locations free from frequent severe vibration.

     product Display

    cjx2-d-ac-contactor-right-view
    cjx2-d-ac-contactor-top-view

    Technical Parameters

    Parameters GN30-12/400-12.5 GN30-12/630-20 GN30-12/1000-31.5 GN30-12/1250-31.5 GN30-12/2000-31.5 GN30-12/3150-31.5
    GN30-12D/400-12.5 GN30-12D/630-20 GN30-12D/1000-31.5 GN30-12D/1250-31.5 GN30-12D/2000-31.5 GN30-12D/3150-31.5
    Rated Voltage (kV) 12 
    Maximum Voltage (kV) 11.5 
    Rated Current (A) 400  630  1000  1250  2000  3150 
    Thermal Withstand Current (kA) 12.5  20  31.5 
    Thermal Withstand Duration (s)
    Rated Peak Withstand Current (kA) 31.5  50  80 
    Rated Insulation Level Lightning Impulse Withstand Voltage (kV) 75 
    1min Power Frequency Withstand Voltage (kV) 42 

    Outline and Installation Dimension

    CJX2-D-4
    Model L L1 L2 A D n B C
    GN30-12/630 210  680  726  820  45  550 
    230  720  766  860  45 
    250  760  806  900  45 
    GN30-12/1000, 1250 210  680  726  820  40  80  575 
    230  720  766  860  40  80 
    250  760  806  900  40  80 
    CJX2-D-4
    Model L L1 L2 A D n B
    GN30-12D/630 210  680  726  820  45 
    230  720  766  860  45 
    250  760  806  900  45 
    GN30-12D/1000, 1250 210  680  726  820  40  80 
    230  720  766  860  40  80 
    250  760  806  900  40  80 

    Main Structure and Working Principle

    The GN30-12 series disconnector is a new rotary-type disconnector. Its main body is fixed to the upper and lower planes of the base frame via two sets of insulators, separated completely by a partition plate mounted on the base. Opening and closing operations are achieved by rotating the contact blade.
    The GN30-12D variant adds an earthing switch to meet different switchgear requirements. With contacts installed on both upper and lower planes, live and non-live parts are fully isolated inside the switchgear, ensuring absolute safety for maintenance personnel.
    The conductive part consists mainly of contact blades and contacts. Each blade, made of two copper plates fixed inside a rotating porcelain bushing with additional magnetic locking plates, has enhanced rigidity and excellent dynamic and thermal stability under short-circuit currents.
    Ball-point contact between blades and contacts reduces assembly difficulty and ensures reliable connection. The switch can be operated with JS×GN-12 or CS6-2 operating mechanisms, or with custom-designed mechanisms.