FZN25-12 Indoor AC High-Voltage Vacuum Load Switch
Type & Meaning

| F | Load Break Switch |
| Z | Vacuum |
| N | Indoor |
| 25 | Design Serial Number |
| 12 | Rated Voltage (kV) |
| D | Earthing Switch (Optional) |
| T | Spring Operating Mechanism |
| 630 | Rated Current (A) |
| 20 | Rated Short-time Withstand Current (kA) |
Basic Structure
The FZN25-12 is a frame-assembled load break switch. Moving/fixed contacts in each phase are enclosed in a vacuum interrupter, mounted with conductors on an integral insulator. The interrupter connects to a rear vertical disconnector via conductors. The disconnector is housed in a semi-enclosed insulator fixed to the metal frame. A side-mounted spring operating mechanism extends service life. A removable fuse assembly forms a switch-fuse combination. The frame includes an earthing arm, mechanism, and interlocks. A transparent flame-retardant shield ensures safety, and a bottom earthing contact enables integrated earthing switch versions.
1.Uses vacuum interrupter for strong arc extinction, reliable and safe performance.
2.Integrated load break switch, disconnector, and mechanism for simple one-step operation with visible break; optional earthing switch with interlock.
3.Supports manual/motorized operation with reliable interlocks, simplifying switchgear design.
4.Fully insulated design (SMC supports) with conical insulators and transparent shield, ideal for armored switchgear.
5.Flexible installation (front/side mount), easy maintenance and fuse replacement.

1.Upper contact base of disconnector
2.Insulating support frame
3.Transparent glass shield
4.Metal frame
5.Conductive tube of disconnector
6.Lower contact base of disconnector
7.Vacuum interrupter
8.Lower outlet base of vacuum interrupter
9.Drive unit of vacuum load break switch
10.Fuse
11.Tripping unit
12.Earthing switch
13.Operation hole for earthing switch
14.Cabinet door lock pin
15.Manual trip button
16.Operation hole for charging & closing
product Display
Technical Parameters
1.Main Electrical Technical Parameters
| Parameters | Unit | Model | ||
| FZN25-12D/T630 | FZRN25-12D/T200 | |||
| Rated Voltage | kV | 12 | 12 | |
| Rated Frequency | Hz | 50 | 50 | |
| Rated Current | A | 630 | 200 | |
| Rated Breaking Current | Active Load Current | A | 630 | |
| Closed-loop Current | A | 630 | ||
| No-load Transformer Capacity | kVA | 1600 | ||
| Cable Charging Current | A | 10 | ||
| Rated Transfer Current | A | 1700 | ||
| Rated Short-time Withstand Current (4s) | kA | 20(25) | ||
| Rated Peak Withstand Current | 50(63) | |||
| Rated Short-circuit Breaking Current | kA | 31.5 | ||
| Rated Short-circuit Making Current | kA | 50(63) | ||
| Rated Short-time (1min) Power Frequency Withstand Voltage | kV | 42/48 | ||
| Rated Lightning Impulse Withstand Voltage (Peak) | kV | 75/85 | ||
| Notes: 1) The rated short-circuit duration for the earthing switch is 2 seconds. 2) The 1min power frequency withstand voltage across the interrupter break is 35kV. |
||||
2. Main Mechanical Characteristic Parameters
| Parameters | Unit | Value | Note |
| Vacuum interrupter contact gap | mm | 6+(1to 0) | |
| Vacuum interrupter contact stroke | mm | -2+(1 to 0) | Measured contact spring compression stroke |
| Disconnector break gap | mm | ≥130 | |
| Phase-to-phase center distance | mm | 210±1 | |
| 3-pole closing non-synchronism of vacuum interrupter | ms | ≤3 | |
| Allowable contact closing bounce time of vacuum interrupter | ms | ≤3 | |
| Average closing speed of vacuum interrupter | m/s | 0.6±0.2 | |
| Average opening speed of vacuum interrupter | m/s | 0.9±0.2 | |
| Conductive loop resistance per pole | μΩ | ≤180 | |
| Maximum operating torque for manual operation | Nm | ≤160 | |
| Mechanical life | times | 10000 |
3. Motor Technical Parameters
| Rated Voltage | Rated Output Power | Normal Operating Voltage Range | ||
| ≈220 | 70W | 85%-100% of rated voltage | ||
4. Shunt Trip Unit Parameters
| Rated Voltage | Normal Operating Voltage Range | |||
| DC 220 DC 110V | 80%-120% of rated voltage | |||
For the current-limiting fuse in the load break switch-fuse combination unit, the rated current of the fuse link shall be selected according to the transformer capacity. The reference parameters for selection are as follows:
| Transformer Capacity (kVA) | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 750/800 | 1000 | 1250 | 1600 | 2000 |
| Fuse Rated Current (A) | 10 | 12.5 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 | 160 | 200 |
Outline and Installation Dimension