FK(R)N12-12 High Voltage Air Load Breaker Fuse Switch

The FKN12-12D load switch and FKRN12-12D switch-fuse combination are designed for 12kV three-phase distribution systems, suitable for transformer, cable, and line control. With rated currents of 630A (FKN) and 125A (FKRN), they feature high insulation, spring-operated mechanisms, and reliable arc extinction in bell-shaped covers. Compact and interlocked, they offer 2000 mechanical operations and withstand harsh environments (–25°C to +40°C, ≤2000m). Ideal for substations and ring networks, these GB/T and IEC-compliant switches ensure safe load switching, overload protection, and short-circuit interruption in urban and industrial applications.

    Type & Meaning

    CJX2-D-4
    1 Rated short-time withstand current (kA)
    2 Rated current (A)
    3 Spring mechanism
    4 Earthing switch (optional)
    5 Rated voltage (kV)
    6 Design No.
    7 Indoor
    8 Air medium
    9 Load switch
    CJX2-D-4
    1 Rated short-circuit breaking current (kA)
    2 Rated current of the maximum fuse equipped (A)
    3 Spring mechanism
    4 Earthing switch (optional)
    5 Rated voltage (kV)
    6 Design No.
    7 Indoor
    8 With fuse holder
    9 Air medium
    10 Load switch

    Ambient conditions

    1)Ambient temperature: within -25℃~+40℃;
    2)Altitude: ≤ 2000m;
    3)Ambient humidity: daily mean relative humidity ≤ 95% and monthly mean ≤ 90%;
    4)Seismic intensity: ≤ Ms8;
    5)Anti-fouling level: Class Ⅱ;
    6)The operation site should be free of flammable or explosive danger, no water vapor or chemical corrosive gas, no violent vibration.
    Note: Please negotiate with the manufacturer if beyond the above-mentioned environmental conditions.

     product Display

    cjx2-d-ac-contactor-right-view
    cjx2-d-ac-contactor-top-view

    Technical Parameters

    ☆ Technical parameters of FKN12-12D series switch and FKRN12-12D series switch-fuse combinations are shown in Table 1

    No. ltem Unit FKN12-12D FKRN12-12D
    1 Rated voltage kV 12 12
    2 Rated frequency Hz 50 50
    3 Rated current A 630 125
    4 Rated insulation level 1min power-frequency withstand voltage To-ground, phase-to-phase kV 42 42
    lsolating distance 48 48
    Lightning impulse withstand voltage (peak) To-ground, phase-to-phase 75 75
    lsolating distance 85 85
    5 Rated short-time withstand current (kA) Load switch kA 25
    Earthing switch 20
    6 Rated short-circuit duration (short-time withstand time) Load switch S 4
    Earthing switch 2
    7 Rated short-circuit making current (peak) 50
    8 Rated breaking current Active load breaking current A 630
    Closed loop breaking current 630
    Cable charging current 10
    Breaking capacity of no-load transformer kVA 1250
    9 Rated short-circuit breaking current (current-limit fuse) kA 31.5
    10 Rated transfer current A 1200
    11 Mechanical endurance time 2000 2000

    ☆ Mechanical properties are shown in Table 2

    No. ltem Unit Parameter
    1 Isolating distance mm ≥175
    2 Phase-to-phase central distance 210±2
    3 Phase-to-phase air clearance ≥125
    4 Travel 210±4
    5 Overtravel ≥40
    6 Out of simultaneity of three-phase closing ms ≤10
    7 Out of simultaneity of three-phase opening ≤15
    8 Inherent opening time of shunt release 40~65
    9 Main circuit resistance μΩ ≤130

    ☆ For the current-limiting fuse in the switch-fuse combinations, the rated current of the fuse-link is selected based on the transformer capacity, and the reference parameters for selection are shown in Table 3

    Transformer capacity (kVA) 100 125 160 200 250 315 400 500 630 750/800 1000 1250
    Rated current of fuse (A) 10 12.5 16 20 25 31.5 40 50 63 80 100 125

    Outline and Installation Dimension

    CJX2-D-4