FK(R)N12-12 High Voltage Air Load Breaker Fuse Switch
Type & Meaning

| 1 | Rated short-time withstand current (kA) |
| 2 | Rated current (A) |
| 3 | Spring mechanism |
| 4 | Earthing switch (optional) |
| 5 | Rated voltage (kV) |
| 6 | Design No. |
| 7 | Indoor |
| 8 | Air medium |
| 9 | Load switch |

| 1 | Rated short-circuit breaking current (kA) |
| 2 | Rated current of the maximum fuse equipped (A) |
| 3 | Spring mechanism |
| 4 | Earthing switch (optional) |
| 5 | Rated voltage (kV) |
| 6 | Design No. |
| 7 | Indoor |
| 8 | With fuse holder |
| 9 | Air medium |
| 10 | Load switch |
Ambient conditions
1)Ambient temperature: within -25℃~+40℃;
2)Altitude: ≤ 2000m;
3)Ambient humidity: daily mean relative humidity ≤ 95% and monthly mean ≤ 90%;
4)Seismic intensity: ≤ Ms8;
5)Anti-fouling level: Class Ⅱ;
6)The operation site should be free of flammable or explosive danger, no water vapor or chemical corrosive gas, no violent vibration.
Note: Please negotiate with the manufacturer if beyond the above-mentioned environmental conditions.
product Display
Technical Parameters
☆ Technical parameters of FKN12-12D series switch and FKRN12-12D series switch-fuse combinations are shown in Table 1
| No. | ltem | Unit | FKN12-12D | FKRN12-12D | ||
| 1 | Rated voltage | kV | 12 | 12 | ||
| 2 | Rated frequency | Hz | 50 | 50 | ||
| 3 | Rated current | A | 630 | 125 | ||
| 4 | Rated insulation level | 1min power-frequency withstand voltage | To-ground, phase-to-phase | kV | 42 | 42 |
| lsolating distance | 48 | 48 | ||||
| Lightning impulse withstand voltage (peak) | To-ground, phase-to-phase | 75 | 75 | |||
| lsolating distance | 85 | 85 | ||||
| 5 | Rated short-time withstand current (kA) | Load switch | kA | 25 | ||
| Earthing switch | 20 | |||||
| 6 | Rated short-circuit duration (short-time withstand time) | Load switch | S | 4 | ||
| Earthing switch | 2 | |||||
| 7 | Rated short-circuit making current (peak) | 50 | ||||
| 8 | Rated breaking current | Active load breaking current | A | 630 | ||
| Closed loop breaking current | 630 | |||||
| Cable charging current | 10 | |||||
| Breaking capacity of no-load transformer | kVA | 1250 | ||||
| 9 | Rated short-circuit breaking current (current-limit fuse) | kA | 31.5 | |||
| 10 | Rated transfer current | A | 1200 | |||
| 11 | Mechanical endurance | time | 2000 | 2000 | ||
☆ Mechanical properties are shown in Table 2
| No. | ltem | Unit | Parameter |
| 1 | Isolating distance | mm | ≥175 |
| 2 | Phase-to-phase central distance | 210±2 | |
| 3 | Phase-to-phase air clearance | ≥125 | |
| 4 | Travel | 210±4 | |
| 5 | Overtravel | ≥40 | |
| 6 | Out of simultaneity of three-phase closing | ms | ≤10 |
| 7 | Out of simultaneity of three-phase opening | ≤15 | |
| 8 | Inherent opening time of shunt release | 40~65 | |
| 9 | Main circuit resistance | μΩ | ≤130 |
☆ For the current-limiting fuse in the switch-fuse combinations, the rated current of the fuse-link is selected based on the transformer capacity, and the reference parameters for selection are shown in Table 3
| Transformer capacity (kVA) | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 750/800 | 1000 | 1250 |
| Rated current of fuse (A) | 10 | 12.5 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 |
Outline and Installation Dimension