CJX2-F Series AC Contactor for Motor Control
Application
CJX2-F series AC contactors (the following is called a contactor) are used in 50Hz or 60Hz circuits. If equipped with a special coil, they can be used in circuits with a frequency of 40-400Hz, with a voltage up to 660V and a current up to 630A. They are used for making and breaking the main circuit, as well as for frequently starting and controlling motors.
They can be combined with general electrical equipment such as various relays, which can be used to control various electrical equipment, motors, and circuits. With auxiliary contact groups, pneumatic time-delay heads, and mechanical interlocks, they can also form mechanically interlocked contactors and star-delta starters. When combined with a thermal relay, they can form a magnetic starter.
Type & Meaning
CJ X2 - F □
1 2 3 4
| 1 | AC contactor |
| 2 | minature |
| 3 | series code |
| 4 | rated working current |
Features
With fine and compact structure, functional molding, and coordinated assembly stereoscopic layout, the contactor product with a triple, triad wiring structure is of linear motion type, and the contact features double-breaking points. A mechanical interlock mechanism is added between two contactors to form a reversible shift contactor.
product Display
Technical Parameters
Table1
| Type | CJX2-F115 | CJX2-F150 | CJX2-F185 | CJX2-F225 | CJX2-F265 | CJX2-F330 | CJX2-F400 | CJX2-F500 | CJX2-F630 | |||
| Rated operational current | AC-3 | 380V | 115 | 150 | 185 | 225 | 265 | 330 | 400 | 500 | 630 | |
| 660V | 86 | 107 | 118 | 135 | 170 | 325 | 305 | 355 | 460 | |||
| AC-4 | 380V | 52 | 60 | 79 | 85 | 105 | 217 | 138 | 147 | 188 | ||
| 660V | 49 | 61 | 69 | 82 | 98 | 118 | 135 | 145 | 170 | |||
| controlled squirrel-cage asynchronous motor's max power pe(W) |
AC-3 | 380V | 55 | 75 | 90 | 110 | 132 | 160 | 200 | 250 | 335 | |
| 660V | 80 | 100 | 110 | 129 | 160 | 220 | 280 | 335 | 450 | |||
| AC-4 | 380V | 25 | 30 | 40 | 45 | 55 | 63 | 75 | 80 | 100 | ||
| 660V | 45 | 55 | 63 | 75 | 90 | 110 | 129 | 140 | 160 | |||
| Conventional thermal current (Ith) | 200 | 250 | 275 | 315 | 350 | 450 | 500 | 700 | 1000 | |||
| Vrated operational voltage (Ue) | 380,660 | |||||||||||
| Rated insulation voltage (V) | 660 | |||||||||||
| operating frequency | IEC947,GB14048 | |||||||||||
| AC-3 | Electrical endurance | 60×10° | 50×10⁴ | 30×10⁴ | 20×10⁴ | |||||||
| Switching frequency | 600 | 300 | ||||||||||
| AC-4 | Electrical endurance | 15×10⁴ | 8×10⁴ | 5×10⁴ | ||||||||
| Switching frequency | 150 | |||||||||||
| Mechanical endurance | Time | 3×10⁶ | 1×10⁶ | |||||||||
| Auxiliary contacts |
Rated heating current(Ith)A | 10 | ||||||||||
| Electrical endurance | 60×10⁴ | 50×10⁴ | 30×10⁴ | 20×10⁴ | ||||||||
Specification of coil
| Type | CJX2-09 | CJX2-12 | CJX2-18 | CJX2-25 | CJX2-32 | CJX2-40 | CJX2-50 | CJX2-63 | CJX2-80 | CJX2-95 | ||
| Close voltage 50/60Hz(V) | (0.85~1.1)Us | |||||||||||
| Release voltage 50/60Hz(V) | (0.2~0.75)Us | |||||||||||
| Coil power | 50Hz | Closing(VA) | 70 | 70 | 70 | 110 | 110 | 200 | 200 | 200 | 200 | 200 |
| Closed(VA) | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 20 | 20 | ||
| 60Hz | Closing(VA) | 80 | 80 | 80 | 115 | 115 | 200 | 200 | 200 | 200 | 200 | |
| Closed(VA) | 8 | 8 | 8 | 11 | 11 | 20 | 20 | 20 | 200 | 200 | ||
| Consumption(W) | 1.8-2.7 | 1.8-2.7 | 1.8-2.7 | 3~4 | 3~4 | 6~10 | 6~10 | 6~10 | 6~10 | 6~10 | ||
Outline and Installation Dimension
CJX2-F115-F330 outline and installation dimensions are shown in Figure 1 and Table 2.

| Type | a max | b max | b1 max | c max | G | L | P | Q | Q1 | S | X | Z | Y | f max | k max |
| CJX2-F115 | 165 | 164 | 137 | 167 | 80±0.8 | 108 | 37 | 29.5 | 60 | 15 | 57 | 26.5 | M6×15 | 133 | 40 |
| CJX2-F150 | 165 | 172 | 137 | 167 | 80±0.8 | 108 | 40 | 26.5 | 57.5 | 20 | 57 | 26.5 | M6×20 | 133 | 40 |
| CJX2-F185 | 171 | 176 | 137 | 181 | 80±0.8 | 114 | 40 | 30 | 60 | 20 | 59.5 | 29 | M6×20 | 133 | 40 |
| CJX2-F225 | 171 | 199 | 137 | 181 | 80±0.8 | 114 | 48 | 22 | 52 | 25 | 59.5 | 29 | M6×30 | 133 | 40 |
| CJX2-F265 | 204 | 205 | 145 | 210 | 96±1.1 | 143 | 48 | 39 | 66.5 | 25 | 61 | 44.5 | M6×30 | 147 | 50 |
| CJX2-F330 | 209 | 209 | 145 | 216 | 96±1.1 | 148 | 48 | 36 | 74 | 25 | 67 | 50.5 | M6×30 | 147 | 60 |
Note: fmin represents the required space for coil replacement, Kmin represents the minimum electrical clearance, and the remaining text refers to the clamp plate wiring.
CJX2-F400-F500 outline and installation dimensions are shown in Figure 2 and Table 3 and Table 4.

| Type | amax | bmax | cmax | fmax | kmax | S | J | L | P | Q | Q1 |
| CJX2-F400 | 213 | 206 | 213 | 119 | 70 | 25 | 19.5 | 14.5 | 48 | 43 | 74 |
| CJX2-F500 | 233 | 238 | 226 | 141 | 70 | 30 | 39.5 | 146 | 55 | 46 | 77 |
| Type | Size No. | Nominal Value | max | min | |||||||
| CJX2-F400 | G | 80 | 102 | 66 | |||||||
| G1 | 170 | 192 | 156 | ||||||||
| CJX2-F500 | G | 80 | 120 | 66 | |||||||
| G1 | 170 | 210 | 156 | ||||||||
CJX2-F630 outline and installation dimensions are shown in Figure 3 and Table 5.

| Size No. | Nominal Value | max | min |
| G | 180 | 195 | 100 |