CJX1 (3TB) Series AC Contactors 9-400A 380V AC-3
Operating Conditions
1.The altitude of the site of installation does not exceed 2000 meters above sea level;
2.The ambient air temperature: -25~+55℃;
3.Relative humidity does not exceed 50% at +40℃ and 90% at +25℃.
4.Atmospheric conditions: the air does not contain any explosive medium, corrosive gases and conductive dust;
5.Never be shocked and vibrate obviously;
6.Never be wetted by rain and snow.
Technical Parameters
| Type | CJX1-9 3TB40 |
CJX1-12 3TB41 |
CJX1-16 3TB42 |
CJX1-22 3TB43 |
CJX1-32 3TB44 |
||||
| Rated insulation voltage (V) | 660 | 660 | 660 | 660 | 660 | ||||
| Rated operational current (380V) (A) | AC-3 | 9 | 12 | 16 | 22 | 32 | |||
| AC-4 | 3.3 | 4.3 | 7.7 | 8.5 | 15.6 | ||||
| Rated outputs of three-phase motors at 50Hz (KW) | AC-3 | 230/220V 400/380V 500V 690/660V 1000V |
2.4 4 5.5 5.5 - |
3.3 5.5 7.5 7.5 - |
4 7.5 10 11 - |
6.1 11 11 11 - |
8.5 15 21 23 - |
||
| AC-4 | 400/380V 690/660V |
1.4 2.4 |
1.9 3.3 |
3.5 6 |
4 6.6 |
7.5 13 |
|||
| Mechanical endurance (×10⁶) | 10 | 10 | 10 | 10 | 10 | ||||
| Electrical endurance (×10⁶) | AC-3 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | |||
| AC-4 | 0.2 | 0.2 | 0.2 | 0.2 | 0.2 | ||||
| Switching frequency (1/h) | AC-3 | 1000 | 1000 | 750 | 750 | 750 | |||
| AC-4 | 250 | 250 | 250 | 250 | 250 | ||||
| Coil voltage tolerance | (0.8~1.1) Us | ||||||||
| Power consumotion of coil (50Hz) (AC) | Closed (VA) | 10 | 10 | 10 | 10 | 10 | |||
| Power Factor (p.f.) | 0.29 | 0.29 | 0.29 | 0.29 | 0.29 | ||||
| Closing (VA) | 68 | 68 | 68 | 68 | 68 | ||||
| Power Factor (p.f.) | 0.82 | 0.82 | 0.82 | 0.82 | 0.82 | ||||
| Convention althermal current (A) | 20 | 20 | 30 | 30 | 45 | ||||
| Conventional thermal current of auxiliary contacts (A) | 10 | 10 | 10 | 10 | 10 | ||||
| Rated operational current of auxiliary contacts (A) | AC-15 380/220V | 6-10 | 6-10 | 6-10 | 6-10 | 4-6 | |||
| Weight (kg) | 0.43 | 0.43 | 0.49 | 0.49 | 0.7 | ||||
| Order No.suffixes for rated control voltages for coils (AC) 3TF40…-0X□□ 3TF44…-0X□□ |
Coil for 50Hz AC V |
Coil for 50Hz/60Hz AC V |
|||||||
| 24 B0 42 D0 110 F0 220 M0 230 UO 380 Q0 |
24 C1 42 D1 110 G1 220 P1 240 R1 |
||||||||
product Display
3TB40-3TB44 Outline and Installation Dimension

| Type | a | b | c | d | e | f | g |
| 3TB40,3TB41 | 79 | 60 | 46 | 35 | *90 106 | 7.5 | Φ5 |
| 3TB42,3TB43 | 89 | 75 | 46 | 35 | 116 | 8 | Φ5 |
| 3TB44 | 90 | 75 | 74 | 50 | 109 | 8 | Φ5 |
* Size 90 is suitable for 3TB4010, 3TB4001, 3TB4110, 3TB4101
Size 106 is suitable for 3TB4011, 3TB4022, 3TB4111, 3TB4122
Permissible Mounting Position
The contactors are designed for operation on vertical mounting surface.