China VSB-12 Indoor High-Voltage Vacuum Circuit Breaker Suppliers - Reliable Factory for 12kV Power Systems

The VSB-12 Indoor High-Voltage Vacuum Circuit Breaker is a robust solution tailored for 12kV power systems, making it an ideal choice for various indoor applications. Manufactured by top suppliers in China, this circuit breaker offers a range of rated currents from 630A to 4000A and boasts a short-circuit breaking capacity of up to 40kA. Designed for reliability, the VSB-12 ensures high insulation strength, mechanical endurance of 20,000 operations, and minimal contact resistance. It supports both AC and DC control voltages, featuring rapid opening and closing times and is engineered for long-term stability even under frequent switching conditions. Choose our factory for quality products that meet your high-voltage needs

    Type Designation

    Brand: MINGRI
    Product Name: High-Voltage Vacuum Circuit Breaker
    Model: VSB-12
    Rated Voltage: 12kV
    Rated Current: 63A
    Rated Frequency: 50Hz
    Altitude: ≤1000 meters
    Mechanical Life: 20,000 operations

    Technical Parameters

    No. Item Unit Value
    1 Rated Voltage kV 12
    2 Maximum Operating Voltage kV 12
    3 Rated Current A 630
    1250
    630 1250
    1600 2000
    2500 3150
    1250 1600
    2000 2500
    3150 4000
    4 Rated Short-Circuit Breaking Current (Rated Short-Time Withstand Current - RMS Value) kA 20/25 31.5 40
    5 Rated Short-Circuit Making Current (Peak) kA 50/63 80 100
    6 Rated Peak Withstand Current (Rated Peak Withstand Current - Peak) kA 50/63 80 100
    7 4S Rated Short-Circuit Withstand Voltage kA 20/25 31.5 40
    8 Rated Insulation Level Power-Frequency Withstand Voltage (1min) (Before and After Rated Breaking) kV Phase-to-Earth 42 (Across Isolating Distance 48)
    Impulse Withstand Voltage (Before and After Rated Breaking) / Rated Lightning Impulse Withstand Voltage (Peak) Phase-to-Earth 75 (Across Isolating Distance 85)
    9 Rated Short-Time Withstand Current Duration s 4
    10 Rated Operating Sequence O-0.3s-CO-180s-CO
    11 Mechanical Life time 20,000
    12 Rated Short-Circuit Current Breaking Operations time 50
    13 Operating Mechanism Rated Closing Voltage (DC) V AC、DC 110, 220
    14 Operating Mechanism Rated Opening Voltage (DC) V AC、DC 110, 220
    15 Contact Gap mm 11±1
    16 Over-Travel (Contact Spring Compression Length) mm 3.5±0.5
    17 Three-Phase Contact Bounce Time (During Opening/Closing) ms ≤2
    18 Contact Bounce Time During Closing ms ≤2
    19 Average Opening Speed m/s 0.9–1.2
    Average Closing Speed m/s 0.5–0.8
    20 Opening Time At Maximum Operating Voltage s ≤0.05
    21 At Minimum Operating Voltage ≤0.08
    22 Closing Time s 0.1
    23 Main Circuit Resistance μΩ 630 ≤50 1250 ≤45
    24 Permissible Cumulative Wear Thickness of Moving/Fixed Contacts mm 3

    Product Display

    VSB-12 High-Voltage Vacuum Circuit Breaker
    VSB-12 Indoor High-Voltage VCB

    Outline and Installation Dimension

    Inside the brackets: 275mm phase spacing

    VSB-12 Outline and Installation Dimension

    Ordering Instructions

    Order Specifications Required from Customers:
    a) Product Name: Model Number. Rated Current;
    b) Rated Current. Number of Poles;
    c) Minimum Order Quantity.

    Frequently Asked Questions (FAQ)

    Q What is the rated voltage of the VSB-12 High-Voltage Vacuum Circuit Breaker?
    The VSB-12 has a rated voltage of 12kV and a maximum operating voltage of 12kV, making it suitable for medium-voltage distribution systems.
    Q What is the mechanical life of the VSB-12 circuit breaker?
    The VSB-12 is rated for 20,000 mechanical operations, ensuring long-term reliable performance in demanding environments.
    Q What operating voltages are supported for the closing and opening mechanisms?
    Both the rated closing and opening voltages support AC and DC 110V / 220V, providing flexible compatibility with different control systems.
    Q What is the rated short-circuit breaking current of the VSB-12?
    The VSB-12 supports rated short-circuit breaking currents of 20/25 kA, 31.5 kA, and 40 kA depending on the configuration selected, meeting various fault interruption requirements.
    Q What is the rated operating sequence of the VSB-12?
    The rated operating sequence is O – 0.3s – CO – 180s – CO, which defines the standard open-close cycle timing for safe and reliable circuit interruption.
    Q What information is required when placing an order for the VSB-12?
    When ordering, customers are required to provide: product name and model number with rated current, the number of poles, and the minimum order quantity. Please contact us with these details to receive an accurate quotation.