China SJKQ2 Dual Power Automatic Transfer Switch - Reliable Factory Suppliers for Critical Backup Systems
Type Designation

| 1 | Manufacturer Code |
| 2 | Auto-Transfer Function |
| 3 | Derivative Code: (): NCCB; W Compact Type; W1: Economy Type; W2: Smart Type (Undervoltage / Phase-Loss / Off / Fire Protection) |
| 4 | Function Code: R – Grid-to-Grid (Optional); F – Grid-to-Generator; M – Terminal Type (Optional); Y – Integrated Smart Type (Off / Fire Protection / Undervoltage); N – Split Smart Type (Off / Fire Protection / Undervoltage) |
| 5 | Frame Size Current |
| 6 | Number of Poles |
| 7 | Rated Current (In) |
Technical Parameters
| Rated current | 100A | 160A | 250A | 630A | 1600A | 3200A |
| Rated voltage | AC 400V | |||||
| Rated Insulation Voltage (Ui) | 500V | 800V | ||||
| Rated Impulse Withstand Voltage (Uimp) | 6KV | 8KV | ||||
| Rated Short-time Withstand Current (Icw) | 5KA | 10KA | 16KA | |||
| Switch Time | <3s | 5s | ||||
| Rated Control Voltage | AC 230V | |||||
| Ambient Temperature | The upper limit is +40°C, the average value does not exceed +35°C within 24 hours; the lower limit is -5°C. | |||||
| Altitude | The altitude of the installation site does not exceed 2000m. | |||||
| Installation Environment | No explosive atmosphere environment. No rain intrusion environment. | |||||
| Power Supply Voltage Deviation | <85% Ue | |||||
| Using Category | AC-33iB | |||||
| Installation Category | II | |||||
| Pollution Degree | 3 | |||||
Product Display
Main Circuit Wiring Diagram & External Power ON Indicator

- 1. Normal Neutral Line
- 2. Normal Source ON Indicator
- 3. Alternate Neutral Line
- 4. Alternate Source ON Indicator
Terminal Diagram
If the user requires fire protection and power generation functions, please consult with the manufacturer for customization. The wiring diagram is as follows:
Outline and Installation Dimensions

Installation Dimensions
SJKQ2 Automatic Power Transfer Switch Installation Dimensions
| Model / Dimensions | W | W1 | L | L1 | H |
| SJKQ2-100/3P | 290 | 253 | 205 | 186 | 120 |
| SJKQ2-100/4P | 320 | 282 | 205 | 186 | 120 |
| SJKQ2-225/3P | 330 | 296 | 215 | 195 | 140 |
| SJKQ2-225/4P | 365 | 333 | 215 | 195 | 140 |
| SJKQ2-400/3P | 465 | 410 | 310 | 285 | 190 |
| SJKQ2-400/4P | 508 | 455 | 310 | 285 | 190 |
| SJKQ2-630/3P | 528 | 478 | 318 | 295 | 195 |
| SJKQ2-630/4P | 588 | 535 | 318 | 295 | 195 |
| SJKQ2-800/3P | 608 | 556 | 334 | 310 | 190 |
| SJKQ2-800/4P | 678 | 626 | 334 | 310 | 190 |
| SJKQ2-1250/4P | 695 | 642 | 391 | 365 | 288 |
| SJKQ2-1600/4P | 695 | 642 | 391 | 365 | 288 |
Frequently Asked Questions
Q What is the SJKQ2 Dual Power Automatic Transfer Switch used for?
The SJKQ2 is an Automatic Transfer Switch (ATS) designed to automatically switch between two power sources — typically grid-to-grid or grid-to-generator — ensuring uninterrupted power supply to critical loads when the primary source fails.
Q What rated current options are available for the SJKQ2?
The SJKQ2 is available in rated current options of 100A, 160A, 250A, 630A, 1600A, and 3200A, making it suitable for a wide range of industrial and commercial power distribution applications.
Q What is the switching time of the SJKQ2 Automatic Transfer Switch?
For models rated at 100A–250A, the switching time is less than 3 seconds. For models rated at 630A and above, the switching time is 5 seconds, ensuring a fast and reliable power transfer response.
Q Does the SJKQ2 support fire protection and power-off functions?
Yes. The SJKQ2 W2 smart type supports Undervoltage, Phase-Loss, Power-Off, and Fire Protection functions. For fire protection and power generation customization, users should consult the manufacturer directly for the appropriate wiring configuration.
Q What are the installation environment requirements for the SJKQ2?
The SJKQ2 should be installed in environments without explosive atmospheres and without rain intrusion. The ambient temperature upper limit is +40°C (average not exceeding +35°C within 24 hours), the lower limit is -5°C, and the installation altitude should not exceed 2000 meters.
Q What pole configurations are available for the SJKQ2 models?
The SJKQ2 is available in both 3-pole (3P) and 4-pole (4P) configurations across various frame sizes from 100A to 1600A, providing flexible options for three-phase and three-phase-plus-neutral power distribution systems.