China SJKM8 MCCB Suppliers | 100A to 630A Moulded Case Circuit Breaker Factory for Reliable Circuit Protection
Type Designation

| 1 | Manufacturer Code |
| 2 | Molded Case Circuit Breaker Code |
| 3 | Design Code |
| 4 | Frame Size |
| 5 | Short-Circuit Breaking Capacity Level 4 |
| 6 | Operation method 3 |
| 7 | Number of Poles 2 |
| 8 | Trip Unit Method & File Code |
Technical Parameters
| SJKM8 Series Circuit Breaker | SJKM8-100 | SJKM8E-160/250 | SJKM8-160/250 | SJKM8-400 | SJKM8-630 | ||||||||
| Pole Number | 1,2,3,4 | 3 | 3,4 | 3,4 | 3,4 | ||||||||
| Control | Manual | Toggle handle | ■ | ■ | ■ | ■ | ■ | ||||||
| Direct or extended rotary handle | ■ | ■ | ■ | ■ | ■ | ||||||||
| Type | Fixed | Front connection | ■ | ■ | ■ | ■ | ■ | ||||||
| Rear connection | - | ■ | ■ | ■ | ■ | ||||||||
| Plug-in | Front connection | ■ | ■ | ■ | ■ | ■ | |||||||
| Rear connection | - | ■ | ■ | ■ | ■ | ||||||||
| Electrical performance complies with IEC 60947-2 and EN 60947-2 standards | |||||||||||||
| Rated Current (A) In 40℃ | 100 | 160/250 | 160/250 | 400 | 630 | ||||||||
| Rated Insulation Voltage(V) Ui | 690 | 690 | 690 | 690 | 690 | ||||||||
| Rated Impulse Withstand Voltage (kV) Uimp | 6 | 6 | 6 | 6 | 6 | ||||||||
| Rated Working Voltage (V) Ue AC 50/60Hz | 500 | 500 | 500 | 500 | 500 | ||||||||
| Circuit Breaker Type | N | H | N | H | N | H | N | H | N | H | |||
| Ultimate Breaking Capacity (kA rms) Icu | AC 50/60Hz | 220/240V | 50 | 65 | 50 | 85 | 50 | 85 | 85 | 100 | 85 | 100 | |
| 380/400V | 25 | 35 | 25 | 36 | 25 | 36 | 36 | 50 | 36 | 50 | |||
| 415V | 25 | 30 | 25 | 36 | 25 | 36 | 36 | 50 | 36 | 50 | |||
| 440V | 20 | 20 | 20 | 25 | 20 | 25 | 36 | 50 | 36 | 50 | |||
| 500V | 10 | 10 | 8 | 10 | 8 | 10 | 20 | 36 | 20 | 36 | |||
| Service Breaking Capacity (kA rms) lcs | AC 50/60Hz | 220/240V | 25 | 30 | 25 | 43 | 25 | 43 | 43 | 50 | 43 | 50 | |
| 380/400V | 13 | 17 | 13 | 18 | 13 | 18 | 18 | 25 | 18 | 25 | |||
| 415V | 7 | 7 | 13 | 18 | 13 | 18 | 18 | 25 | 18 | 25 | |||
| 440V | 5 | 5 | 10 | 13 | 10 | 13 | 18 | 25 | 18 | 25 | |||
| 500V | 3 | 3 | 4 | 5 | 4 | 5 | 10 | 18 | 10 | 18 | |||
| Isolation Function | ■ | ■ | ■ | ■ | ■ | ||||||||
| Application Category | A | A | A | A | A | ||||||||
| Maximum Expected Maintenance Value (C-O Cycle) | Mechanical | 8500 | 10000 | 10000 | 6000 | 6000 | |||||||
| Electrical 440V In | 4000 | 5000 | 5000 | 1000 | 1000 | ||||||||
| Protection | |||||||||||||
| Release | Thermo-magnetic | Thermo-magnetic | Thermo-magnetic | Thermo-magnetic | Thermo-magnetic | ||||||||
| Overload Protection | Long-time Delay | Ir(In×…) | ■ | ■ | ■ | ■ | ■ | ||||||
| Short-Circuit Protection | Short-time Delay | Isd(In×…) | - | - | - | - | - | ||||||
| Instantaneous | li(In× ·) | ■ | ■ | ■ | ■ | ■ | |||||||
| Leakage Protection | Circuit Breaker with Complete Leakage Protection | - | - | ■ | ■ | ■ | |||||||
| Vigirex Relay | ■ | ■ | ■ | ■ | ■ | ||||||||
| Indication and Control Auxiliaries | |||||||||||||
| Auxiliary Contact (FZ) and Alarm Contact (BJ) | ■ | ■ | ■ | ■ | ■ | ||||||||
| Auxiliary Alarm Contact (FZ/BJ) | ■ | ■ | ■ | ■ | ■ | ||||||||
| Shunt Trip Coil (FL) | ■ | ■ | ■ | ■ | ■ | ||||||||
| Under-Voltage Coil (QY) | ■ | ■ | ■ | ■ | ■ | ||||||||
| Modbus Communication | |||||||||||||
| Pm200 Meter | Electrical Measurement (Current, Voltage, Power, Energy) | ■ | ■ | ■ | ■ | ■ | |||||||
| Mc Multi-Circuit Monitoring Unit | Status | ■ | ■ | ■ | ■ | ■ | |||||||
| Electrical Measurement (Current, Voltage) | ■ | ■ | ■ | ■ | ■ | ||||||||
| Installation | |||||||||||||
| Accessories | Terminal Expansion and Extension | ■ | ■ | ■ | ■ | ■ | |||||||
| Terminal Cover | ■ | ■ | ■ | ■ | ■ | ||||||||
| Phase Separator | ■ | ■ | ■ | ■ | ■ | ||||||||
| Circuit Breaker Type | N/H | N/H | N/H | N/H | N/H | ||||||||
| Dimensions (mm) W×H×D | Fixed Front Connection | 1P | 25×130×60 | - | - | - | - | ||||||
| Fixed Front Connection | 2P | 50×130×60 | - | - | - | - | |||||||
| Fixed Front Connection | 3P | 75×130×60 | 105x165x60 | 105x165×68 | 140x257x103 | 140×257x103 | |||||||
| Fixed Front Connection | 4P | 100×130×60 | - | 140x165x68 | 185×257x103 | 185x257x103 | |||||||
| Weight (kg) | Fixed Front Connection | 1P/2P | 0.28/0.48 | - | - | - | - | ||||||
| Fixed Front Connection | 3P/4P | 0.78/1.0 | 1.3 | 1.6/2.1 | 6.05/7.9 | 6.5/8.7 | |||||||
Product Display
Ambient Temperature
SJKM8-100~630
| Rated current | Environmental temperature | ||||||
| (A) | 40℃ | 45℃ | 50℃ | 55℃ | 60℃ | 65℃ | 70℃ |
| 15 | 15.7 | 15.3 | 15 | 14.7 | 4.6 | 14.2 | 13.8 |
| 20 | 20.4 | 20.2 | 20 | 19.9 | 192 | 18.9 | 16.5 |
| 25 | 25.7 | 25.3 | 25 | 24.7 | 24.5 | 24.3 | 24.0 |
| 30 | 314 | 30.7 | 30 | 294 | 29.1 | 28.5 | 28.0 |
| 40 | 40.9 | 404 | 40 | 39.5 | 38.0 | 376 | 37.1 |
| 50 | 52.1 | 510 | 50 | 49.3 | 48.1 | 473 | 46.6 |
| 60 | 61.8 | 60.9 | 60 | 59.0 | 57.5 | 56.6 | 55.7 |
| 75 | 76.8 | 759 | 75 | 73.5 | 70.4 | 698 | 69.1 |
| 80 | 82.2 | 811 | 80 | 78.5 | 77.3 | 75.7 | 76.1 |
| 100 | 103 | 101 | 100 | 992 | 94.2 | 93.5 | 92.7 |
| 100 | 106.8 | 103.5 | 100 | 96.4 | 92.7 | 88.8 | 84.7 |
| 125 | 134.9 | 130 | 125 | 1198 | 114.3 | 108.5 | 102.5 |
| 160 | 170.9 | 165.5 | 160 | 154.3 | 148.3 | 142.1 | 135.6 |
| 175 | 175 | 168 | 161 | 154 | 146 | 138 | 126 |
| 200 | 215 | 2076 | 200 | 192 | 183.8 | 175.1 | 165.9 |
| 225 | 243.5 | 234.5 | 225 | 215.1 | 204.8 | 193.9 | 1823 |
| 250 | 270.6 | 260.5 | 250 | 239 | 2275 | 2154 | 2026 |
| 250 | 268 | 260 | 250 | 240 | 228 | 218 | 208 |
| 320 | 342 | 333 | 320 | 307 | 291 | 278 | 266 |
| 350 | 375 | 364 | 350 | 336 | 319 | 305 | 291 |
| 400 | 428 | 416 | 400 | 384 | 364 | 348 | 332 |
| 400 | 400 | 390.5 | 381 | 3714 | 3619 | 349.2 | 339.7 |
| 500 | 500 | 488.1 | 476.2 | 464.3 | 4524 | 436.5 | 424.6 |
| 630 | 630 | 65 | 600 | 585 | 570 | 550 | 535 |
SJKM8-100 1P,2P Fixed-type Power Distribution and Motor Protection

- ① Outline Dimensions
- ② Chassis Installation
- ③ DIN Rail Installation
- ④ Front-of-Panel Opening (Small)
- ⑤ Front-of-Panel Opening (Large)
SJKM8-100 3P,4P Fixed-type Power Distribution and Motor Protection

- ① Outline Dimensions
- ② Chassis Installation
- ③ DIN Rail Installation
- ④ Front-of-Panel Opening (Small)
- ⑤ Front-of-Panel Opening (Large)
Frequently Asked Questions
Q
What is the rated current range of the SJKM8 Series Moulded Case Circuit Breaker?
The SJKM8 Series MCCB covers a rated current range from 15A up to 630A at 40℃, with available frame sizes including SJKM8-100, SJKM8E-160/250, SJKM8-160/250, SJKM8-400, and SJKM8-630 to suit various power distribution and motor protection applications.
Q
What international standards does the SJKM8 MCCB comply with?
The SJKM8 Series circuit breaker's electrical performance complies with IEC 60947-2 and EN 60947-2 standards, ensuring reliable and internationally recognized safety performance for industrial and commercial installations.
Q
What is the maximum ultimate breaking capacity (Icu) of the SJKM8 MCCB?
The SJKM8 Series achieves a maximum ultimate breaking capacity (Icu) of up to 100kA rms at 220/240V AC for the H-type in the 400A and 630A frame sizes. At 380/400V, the maximum Icu reaches 50kA rms for H-type units in the 400A and 630A frames.
Q
What installation types and connection methods are available for the SJKM8?
The SJKM8 supports both Fixed and Plug-in installation types, each with Front connection and Rear connection options. Control can be performed via a toggle handle or a direct/extended rotary handle, providing flexible installation solutions for different panel configurations.
Q
Does the SJKM8 support Modbus communication and remote monitoring?
Yes. The SJKM8 Series supports Modbus communication through the Pm200 Meter for electrical measurements including current, voltage, power, and energy, as well as the Mc Multi-Circuit Monitoring Unit for status monitoring and current/voltage measurement across all frame sizes.
Q
How does ambient temperature affect the rated current of the SJKM8 circuit breaker?
The rated current of the SJKM8 decreases as ambient temperature rises above the standard 40℃ reference. For example, a 630A breaker rated at 630A at 40℃ will derate to approximately 535A at 70℃. It is important to consult the ambient temperature derating table to ensure correct breaker selection for high-temperature environments.







Claire
Mr.Fu

Claire