Leave Your Message
Products Categories
Featured Products

China KYN61-40.5 Armoured Moving Type AC Metal Enclosed Switchgear - Suppliers & Factory for High Voltage Solutions

,

The KYN61-40.5 Armoured Moving Type AC Metal Enclosed Switchgear is a premier high-voltage indoor power distribution solution designed for 40.5kV/50Hz systems. This switchgear is highly regarded among power plants, substations, and industrial facilities for its exceptional energy distribution capabilities, circuit protection, and monitoring functions. Manufactured in China, it adheres to stringent standards including GB3906-2006, GB/T11022-1999, and DL/T404-2007, ensuring top-tier performance and reliability. The armoured moving design offers enhanced safety features and durable construction, perfect for frequent switching applications. With its modular withdrawable design, maintenance is simplified without compromising on insulation and arc-quenching performance. Partner with leading suppliers and factories in China for a reliable solution tailored for critical power infrastructure that demands high-voltage control.

,

    Type Designation

    KYN61-40-8
    1 Armored Withdrawable Metal-Clad Switchgear
    2 Withdrawable Type
    3 Usage Conditions: (Indoor)
    4 Design Serial Number
    5 Rated Voltage (kV)
    6 Vacuum Circuit Breaker

    Technical Parameters

    Main Technical Specifications of Spring Operating Mechanism
    Parameter Unit Value
    Rated Operating Voltage Trip Coil V DC220/110   AC220/110
    Close Coil
    Rated Operating Current Trip Coil A 0.96(220V)   1.05(110V)
    Close Coil
    Motor Power (Energy Storage) W 230
    Rated Voltage (Energy Storage Motor) V DC220/110   AC220/110
    Energy Storage Time S ≤12
    Main Technical Specifications of Vacuum Switchgear
    No. Parameter Unit Value
    1 Rated Voltage kV 40.5
    2 Rated Current A 1250, 1600, 2000
    3 Rated Frequency Hz 50
    4 Rated Short-Time Withstand Current kA 20, 25, 31.5
    5 Rated Peak Withstand Current kA 50, 63, 80
    6 Rated Power-Frequency Withstand Voltage kV 95/1min
    7 Rated Lightning Impulse Withstand Voltage kV 185
    8 Rated Short-Circuit Duration S 4
    9 Protection Level IP3X
    Main Technical Specifications of Vacuum Circuit Breaker
    No. Parameter Unit Value
    1 Rated Voltage kV 40.5
    2 Rated Frequency Hz 50
    3 Rated Power-Frequency Withstand Voltage (1min) kV 95/1min
    4 Rated Lightning Impulse Withstand Voltage kV 185
    5 Rated Current A 1250, 1600, 2000
    6 Rated Short-Time Withstand Current kA 20, 25, 31.5
    7 Rated Short-Circuit Breaking Current kA 20, 25, 31.5
    8 Rated Peak Withstand Current kA 50, 63, 80
    9 Rated Short-Circuit Duration ms 4
    10 Opening Time ms 30≤t≤60
    11 Closing Time ms 50≤t≤100
    12 Rated Short-Circuit Breaking Cycles times 20
    13 Mechanical Life times 10000

    Product Display

    KYN61-40-1
    KYN61-40-2
    KYN61-40-3
    KYN61-40-4

    Switchgear Dimensions

    KYN61-40-6
    KYN61-40-7
    • Left figure: Overall Dimensions (W×D×H): 1400×2800×2600mm
    • Right figure: Switchgear Cabinet Structure Diagram
      A. Relay Instrument Room
      B. Busbar Chamber
      C. CB Compartment
      D. Cable Compartment

    Frequently Asked Questions

    QWhat is the rated voltage of the KYN61-40 switchgear?
    The KYN61-40 armored withdrawable metal-clad switchgear has a rated voltage of 40.5 kV, making it suitable for medium-voltage power distribution systems.
    QWhat rated current options are available for the KYN61-40?
    The KYN61-40 is available in rated current options of 1250 A, 1600 A, and 2000 A to accommodate various load requirements.
    QWhat type of circuit breaker is used in the KYN61-40 switchgear?
    The KYN61-40 uses a vacuum circuit breaker (VCB). It features a mechanical life of up to 10,000 operations and a rated short-circuit breaking current of 20, 25, or 31.5 kA.
    QWhat are the overall dimensions of the KYN61-40 switchgear cabinet?
    The overall dimensions (W×D×H) of the KYN61-40 switchgear cabinet are 1400×2800×2600 mm. The cabinet structure includes a Relay Instrument Room, Busbar Chamber, CB Compartment, and Cable Compartment.
    QWhat is the energy storage time of the spring operating mechanism?
    The spring operating mechanism of the KYN61-40 has an energy storage time of no more than 12 seconds (≤12 S), with a motor power of 230 W for energy storage.
    QWhat installation environment is the KYN61-40 switchgear designed for?
    The KYN61-40 is designed for indoor installation environments. It carries a protection level of IP3X and is suitable for use in indoor medium-voltage power distribution substations.