China GN19-12 Indoor High-Voltage Isolating Switch Factory & Suppliers for Reliable Power Solutions

| 1 | Disconnector |
| 2 | Indoor type |
| 3 | Design serial number |
| 4 | Rated voltage |
| 5 | Wall-through type |
| 6 | Rated current |
| 7 | Rated short-time withstand current (4s) |
-
Model Description
- GN19-12: Flat-mounted type; GN19-12C: Wall-through type
- C1: Rotating side at wall-through side
- C2: Breaking side at wall-through side
- C3: Both sides are wall-through type
-
Derivative Model Description
- Anti-pollution type: GN19-12W(C)
- High-altitude type: GN19-12G(C)
- With live-line indicating device: GN19-12X(C)
| Model | Rated Voltage (kV) | Maximum Voltage (kV) | Rated Current (A) | 4s Thermal Withstand Current (RMS) (kA) | Dynamic Withstand Current (Peak) (kA) |
| GN19-12/400-12.5 | 12 | 11.5 | 400 | 12.5 | 31.5 |
| GN19-12/630-20 | 12 | 11.5 | 630 | 20 | 50 |
| GN19-12/1000-31.5 | 12 | 11.5 | 1000 | 31.5 | 80 |
| GN19-12/1250-40 | 12 | 11.5 | 1250 | 40 | 100 |
| GN19-12C/400-12.5 | 12 | 11.5 | 400 | 12.5 | 31.5 |
| GN19-12C/630-20 | 12 | 11.5 | 630 | 20 | 50 |
| GN19-12C/1000-31.5 | 12 | 11.5 | 1000 | 31.5 | 80 |
| GN19-12C/1250-40 | 12 | 11.5 | 1250 | 40 | 100 |

| Model | A | B | C | D | E | F | ||||||
| GN19-12/400 | 450 | 436 | 4-14×24 | 210 | 230 | 250 | 620 | 660 | 700 | 870 | 900 | 940 |
| GN19-12/630 | 470 | 436 | ||||||||||
| GN19-12/(1000 or 1250) | 500 | 530 | 4-18×28 | |||||||||
| GN19-C/400 | 420 | 625 | 4-14×24 | |||||||||
| GN19-C/630 | 420 | 680 | ||||||||||
| GN19-C/(1000 or 1250) | 505 | 745 | 4-18×28 | |||||||||
The GN19-12 series disconnectors are available in flat-mounted (GN19-12) and wall-through (GN19-12C1) versions. Each phase of the GN19-12 conductive part is fixed to the base frame via two post insulators, while the GN19-12C1 uses one insulator and one porcelain bushing. Both types are installed in three parallel phases. The conductive part consists of contact blades and contacts; each contact blade is connected to the main shaft on the base frame via a tie rod insulator. The main shaft links to the CS6-1 operating mechanism through cranks and connecting rods, with a connecting rod (user-supplied) on the mechanism driving the auxiliary switch.
Each contact blade is made of two grooved copper plates, which increases heat dissipation area and mechanical strength, improving dynamic stability. Contact pressure is maintained by contact springs. The 1000A and 1250A versions have magnetic-locking plates at contacts to boost pressure, enhancing dynamic and thermal stability; 400A and 630A versions omit these plates due to lower current ratings and closer blade spacing. The CS6-1 mechanism has a self-locking device to hold the disconnector in open or closed positions.







Claire
Mr.Fu

Claire










