China FZN25-12 Indoor AC High-Voltage Vacuum Load Switch - 12kV, 630A, Reliable Factory Supplier

| F | Load Break Switch |
| Z | Vacuum |
| N | Indoor |
| 25 | Design Serial Number |
| 12 | Rated Voltage (kV) |
| D | Earthing Switch (Optional) |
| T | Spring Operating Mechanism |
| 630 | Rated Current (A) |
| 20 | Rated Short-time Withstand Current (kA) |
The FZN25-12 is a frame-assembled load break switch. Moving/fixed contacts in each phase are enclosed in a vacuum interrupter, mounted with conductors on an integral insulator. The interrupter connects to a rear vertical disconnector via conductors. The disconnector is housed in a semi-enclosed insulator fixed to the metal frame. A side-mounted spring operating mechanism extends service life. A removable fuse assembly forms a switch-fuse combination. The frame includes an earthing arm, mechanism, and interlocks. A transparent flame-retardant shield ensures safety, and a bottom earthing contact enables integrated earthing switch versions.
- Uses vacuum interrupter for strong arc extinction, reliable and safe performance.
- Integrated load break switch, disconnector, and mechanism for simple one-step operation with visible break; optional earthing switch with interlock.
- Supports manual/motorized operation with reliable interlocks, simplifying switchgear design.
- Fully insulated design (SMC supports) with conical insulators and transparent shield, ideal for armored switchgear.
- Flexible installation (front/side mount), easy maintenance and fuse replacement.

- 1. Upper contact base of disconnector
- 2. Insulating support frame
- 3. Transparent glass shield
- 4. Metal frame
- 5. Conductive tube of disconnector
- 6. Lower contact base of disconnector
- 7. Vacuum interrupter
- 8. Lower outlet base of vacuum interrupter
- 9. Drive unit of vacuum load break switch
- 10. Fuse
- 11. Tripping unit
- 12. Earthing switch
- 13. Operation hole for earthing switch
- 14. Cabinet door lock pin
- 15. Manual trip button
- 16. Operation hole for charging & closing
| Parameters | Unit | Model | ||
| FZN25-12D/T630 | FZRN25-12D/T200 | |||
| Rated Voltage | kV | 12 | 12 | |
| Rated Frequency | Hz | 50 | 50 | |
| Rated Current | A | 630 | 200 | |
| Rated Breaking Current | Active Load Current | A | 630 | |
| Closed-loop Current | A | 630 | ||
| No-load Transformer Capacity | kVA | 1600 | ||
| Cable Charging Current | A | 10 | ||
| Rated Transfer Current | A | 1700 | ||
| Rated Short-time Withstand Current (4s) | kA | 20(25) | ||
| Rated Peak Withstand Current | 50(63) | |||
| Rated Short-circuit Breaking Current | kA | 31.5 | ||
| Rated Short-circuit Making Current | kA | 50(63) | ||
| Rated Short-time (1min) Power Frequency Withstand Voltage | kV | 42/48 | ||
| Rated Lightning Impulse Withstand Voltage (Peak) | kV | 75/85 | ||
|
Notes:
1) The rated short-circuit duration for the earthing switch is 2 seconds. 2) The 1min power frequency withstand voltage across the interrupter break is 35kV. |
||||
| Parameters | Unit | Value | Note |
| Vacuum interrupter contact gap | mm | 6+(1to 0) | |
| Vacuum interrupter contact stroke | mm | -2+(1 to 0) | Measured contact spring compression stroke |
| Disconnector break gap | mm | ≥130 | |
| Phase-to-phase center distance | mm | 210±1 | |
| 3-pole closing non-synchronism of vacuum interrupter | ms | ≤3 | |
| Allowable contact closing bounce time of vacuum interrupter | ms | ≤3 | |
| Average closing speed of vacuum interrupter | m/s | 0.6±0.2 | |
| Average opening speed of vacuum interrupter | m/s | 0.9±0.2 | |
| Conductive loop resistance per pole | μΩ | ≤180 | |
| Maximum operating torque for manual operation | Nm | ≤160 | |
| Mechanical life | times | 10000 |
| Rated Voltage | Rated Output Power | Normal Operating Voltage Range |
| ≈220V | 70W | 85%–100% of rated voltage |
| Rated Voltage | Normal Operating Voltage Range |
| DC 220V / DC 110V | 80%–120% of rated voltage |
For the current-limiting fuse in the load break switch-fuse combination unit, the rated current of the fuse link shall be selected according to the transformer capacity. The reference parameters for selection are as follows:
| Transformer Capacity (kVA) | 100 | 125 | 160 | 200 | 250 | 315 | 400 | 500 | 630 | 750/800 | 1000 | 1250 | 1600 | 2000 |
| Fuse Rated Current (A) | 10 | 12.5 | 16 | 20 | 25 | 31.5 | 40 | 50 | 63 | 80 | 100 | 125 | 160 | 200 |