China FZN25-12 Indoor AC High-Voltage Vacuum Load Switch - 12kV, 630A, Reliable Factory Supplier

The FZN25-12 indoor AC high-voltage vacuum load switch, designed for 12kV and 50Hz three-phase networks, is a high-performance solution from trusted China suppliers and factories. Capable of handling load currents and managing short-circuit currents, this switch has a rated capacity of 630A and can withstand short-time currents of 20/25kA. It utilizes advanced vacuum arc-extinguishing technology, ensuring reliable operation. This load switch can be operated both manually and with a motor, making it suitable for demanding environments where maintenance intervals are extended and frequent operation is necessary. Adhering to GB/T and IEC standards, it delivers consistent performance in temperatures ranging from -25℃ to +40℃ and at altitudes up to 2000m, making it an excellent choice for various applications

    Type & Meaning
    CJX2-D-4
    F Load Break Switch
    Z Vacuum
    N Indoor
    25 Design Serial Number
    12 Rated Voltage (kV)
    D Earthing Switch (Optional)
    T Spring Operating Mechanism
    630 Rated Current (A)
    20 Rated Short-time Withstand Current (kA)
    Basic Structure

    The FZN25-12 is a frame-assembled load break switch. Moving/fixed contacts in each phase are enclosed in a vacuum interrupter, mounted with conductors on an integral insulator. The interrupter connects to a rear vertical disconnector via conductors. The disconnector is housed in a semi-enclosed insulator fixed to the metal frame. A side-mounted spring operating mechanism extends service life. A removable fuse assembly forms a switch-fuse combination. The frame includes an earthing arm, mechanism, and interlocks. A transparent flame-retardant shield ensures safety, and a bottom earthing contact enables integrated earthing switch versions.

    • Uses vacuum interrupter for strong arc extinction, reliable and safe performance.
    • Integrated load break switch, disconnector, and mechanism for simple one-step operation with visible break; optional earthing switch with interlock.
    • Supports manual/motorized operation with reliable interlocks, simplifying switchgear design.
    • Fully insulated design (SMC supports) with conical insulators and transparent shield, ideal for armored switchgear.
    • Flexible installation (front/side mount), easy maintenance and fuse replacement.
    FZN25-12 Basic Structure
    • 1. Upper contact base of disconnector
    • 2. Insulating support frame
    • 3. Transparent glass shield
    • 4. Metal frame
    • 5. Conductive tube of disconnector
    • 6. Lower contact base of disconnector
    • 7. Vacuum interrupter
    • 8. Lower outlet base of vacuum interrupter
    • 9. Drive unit of vacuum load break switch
    • 10. Fuse
    • 11. Tripping unit
    • 12. Earthing switch
    • 13. Operation hole for earthing switch
    • 14. Cabinet door lock pin
    • 15. Manual trip button
    • 16. Operation hole for charging & closing
    Product Display
    FZN25-12 Indoor AC HV Vacuum Load Switch - View 1
    FZN25-12 Indoor AC HV Vacuum Load Switch - View 2
    Technical Parameters
    1. Main Electrical Technical Parameters
    Parameters Unit Model
    FZN25-12D/T630 FZRN25-12D/T200
    Rated Voltage kV 12 12
    Rated Frequency Hz 50 50
    Rated Current A 630 200
    Rated Breaking Current Active Load Current A 630
    Closed-loop Current A 630
    No-load Transformer Capacity kVA 1600
    Cable Charging Current A 10
    Rated Transfer Current A 1700
    Rated Short-time Withstand Current (4s) kA 20(25)
    Rated Peak Withstand Current 50(63)
    Rated Short-circuit Breaking Current kA 31.5
    Rated Short-circuit Making Current kA 50(63)
    Rated Short-time (1min) Power Frequency Withstand Voltage kV 42/48
    Rated Lightning Impulse Withstand Voltage (Peak) kV 75/85
    Notes:
    1) The rated short-circuit duration for the earthing switch is 2 seconds.
    2) The 1min power frequency withstand voltage across the interrupter break is 35kV.
    2. Main Mechanical Characteristic Parameters
    Parameters Unit Value Note
    Vacuum interrupter contact gap mm 6+(1to 0)
    Vacuum interrupter contact stroke mm -2+(1 to 0) Measured contact spring compression stroke
    Disconnector break gap mm ≥130
    Phase-to-phase center distance mm 210±1
    3-pole closing non-synchronism of vacuum interrupter ms ≤3
    Allowable contact closing bounce time of vacuum interrupter ms ≤3
    Average closing speed of vacuum interrupter m/s 0.6±0.2
    Average opening speed of vacuum interrupter m/s 0.9±0.2
    Conductive loop resistance per pole μΩ ≤180
    Maximum operating torque for manual operation Nm ≤160
    Mechanical life times 10000
    3. Motor Technical Parameters
    Rated Voltage Rated Output Power Normal Operating Voltage Range
    ≈220V 70W 85%–100% of rated voltage
    4. Shunt Trip Unit Parameters
    Rated Voltage Normal Operating Voltage Range
    DC 220V / DC 110V 80%–120% of rated voltage

    For the current-limiting fuse in the load break switch-fuse combination unit, the rated current of the fuse link shall be selected according to the transformer capacity. The reference parameters for selection are as follows:

    Transformer Capacity (kVA) 100 125 160 200 250 315 400 500 630 750/800 1000 1250 1600 2000
    Fuse Rated Current (A) 10 12.5 16 20 25 31.5 40 50 63 80 100 125 160 200
    Outline and Installation Dimension
    FZN25-12 Outline and Installation Dimension
    Frequently Asked Questions (FAQ)
    What is the FZN25-12 vacuum load break switch used for?
    The FZN25-12 is an indoor AC high-voltage vacuum load break switch designed for 12kV distribution systems. It is used to switch load currents, provide visible disconnection, and optionally incorporate an earthing switch for safe maintenance operations in medium-voltage switchgear.
    What is the rated voltage and current of the FZN25-12?
    The FZN25-12 has a rated voltage of 12kV and a rated current of 630A (for the FZN25-12D/T630 model). The FZRN25-12D/T200 variant offers a rated current of 200A. The rated short-time withstand current is 20kA (4 seconds), with a peak withstand current of 50kA.
    Does the FZN25-12 support motorized operation?
    Yes. The FZN25-12 supports both manual and motorized operation. The motor operates at approximately 220V AC with a rated output power of 70W and a normal operating voltage range of 85%–100% of the rated voltage. The shunt trip unit operates at DC 220V or DC 110V.
    What is the mechanical life of the FZN25-12?
    The FZN25-12 is designed for a mechanical life of 10,000 operations. The side-mounted spring operating mechanism is specifically engineered to extend service life and ensure reliable performance over long-term use in demanding distribution environments.
    How do I select the correct fuse rating for the switch-fuse combination?
    The fuse rated current should be selected based on the transformer capacity. For example, a 100kVA transformer requires a 10A fuse, while a 1600kVA transformer requires a 160A fuse. Refer to the fuse selection table in the Technical Parameters section for full reference values from 100kVA to 2000kVA.
    Is the FZN25-12 suitable for armored switchgear applications?
    Yes. The FZN25-12 features a fully insulated design using SMC supports, conical insulators, and a transparent flame-retardant shield, making it ideal for armored (metal-clad) switchgear. It also supports flexible installation options (front or side mounting) for ease of integration and maintenance.