A9~300 Series AC Contactors 50/60Hz 380V

The A9~300 Series AC Contactors are engineered for 50/60Hz systems, supporting voltages up to 660V and operational currents up to 300A at 380V under AC-3 category. Ideal for long-distance circuit making and breaking, they pair with thermal overload relays or electronic starters for overload protection. Key features include a direct-action double-break contact structure, arc-resistant plastic housing, durable silver alloy contacts, a compact E-shaped iron core, and flexible coil wiring options for easy installation.

    Type & Meaning

    CJX2-D-4
    1 AC contact
    2 Design code
    3 The basic specification code corresponds to the rated working voltage under AC-3 utilization category; and is expressed by the numerical value of the rated operating current at 380V under AC-3 application category.
    4 The main contact pairs are indicated with two figures; the ones place represents NC (normally closed) contact pairs; The tens digit represents NO (normally open) contact pairs;
    5 The auxiliary contact pairs are indicated with two figures; the ones place represents NC (normally closed) contact pairs; For contact pairs, the tens digit represents NO (normally open) contact pairs;

    Main Structure and Working Principle

    1. The contactor features a positive-mounted, direct-action double-break contact structure. Its cover and body are made of arc-resistant plastic. Models A9–16 use natural arc extinguishing, while models A9–26 to 110 incorporate U-shaped arc extinguishing plates within the body to form a sealed arc chamber, delivering excellent arc extinguishing performance with zero arc-over distance. Contacts are made of anti-welding, wear-resistant silver-based alloy, offering good conductivity, long service life, and environmental friendliness. The iron core adopts an E-shaped design for compact size. Two coil wiring options are available: both terminals at one end, or one terminal at each end, ensuring flexible and convenient wiring.
    The base is constructed from glass fiber reinforced plastic, providing high strength and good dielectric properties. Installation can be via screws or DIN rail, enabling quick and easy assembly/disassembly. Live conductive parts are fully enclosed, ensuring high safety performance.
    2. The working principle of the contactor: When the control power to the contactor’s pull-in coil is applied (or removed), the magnetic system generates (or dissipates) electromagnetic force, driving the moving parts to make (or break) the circuit, thus achieving the control objective.

     product Display

    cjx2-d-ac-contactor-right-view
    cjx2-d-ac-contactor-top-view

    Technical Parameters

    a.The installation site elevation shall not exceed 2000 m;
    b.Ambient air temperature shall not exceed +40°C, nor shall it exceed +35°C within 24 hours. The lower limit of ambient air temperature is -5°C;
    c.The relative air humidity at the installation site shall not exceed 50% at a maximum temperature of +40°C. Higher relative humidity is permitted at lower temperatures, e.g., 90% at 20°C. Measures must be taken to prevent dew condensation on the product due to temperature changes;
    d.The installation site pollution class is 3;
    e. The contactor can be mounted vertically or horizontally. If mounted vertically, the gradient between the mounting surface and the vertical plane shall not exceed ±30°; (See Fig. 1)

    CJX2-D-4

    1. The allowable application category of main circuit and the auxiliary circuit of the contactor in the table 1 Table 1 application category of main circuit and the auxiliary circuit of the contactor in the table

    Circuit Application category code Example of the typical usage
    Main Circuit AC-1 Noninductive or the micro ineuductive load,resistance fumace
    AC-2 The starting and breaking of wire winding type asynchronous motor
    AC-3 The starting and breaking during operation of cage asynchronous motor
    AC-4 The starting, plug breaking or reverse revolution, spot moving of cage asynchronous motor
    Auxiliary circuit AC-15 Control AC electromagnet load(>72VA)
    DC-13 Control DC magnet load

    2. Contactor rated insulation voltage (Ui), rated working voltage (Ue), conventional free air heating current (Ith), rated operating current (Ie) and rated insulation class

    Type Frame code Rated insulation voltage UiV Convensional free air heat current Ith AC-3 rated operating current Ie A AC-3 control the max.power KW of generator
    220V 380V 660V 220V 380V 660V
    A9-9 16  1000  26  2.2  5.5 
    A9-12 28  12  12  5.5  6.5 
    A9-16 30  17  17  10  7.5 
    A9-26 26  45  26  26  17  6.5  11  15 
    A9-30 40  65  32  32  21  15  18.5 
    A9-40 65  37  37  25  11  8.5  22 
    A9-50 75  100  50  50  35  15  22  30 
    A9-63 125  65  65  43  18.5  30  37 
    A9-75 125  75  75  46  22  37  40 
    A9-95 110  145  96  96  65  25  45  55 
    A9-110 160  110  110  82  30  55  75 
    A9-145 185  250  145  145  120  40  75  100 
    A9-185 275  185  185  170  50  90  120 
    A9-210 300  350  210  210  210  60  110  150 
    A9-260 400  260  260  260  78  140  190 
    A9-300 450  300  300  280  88  160  220 

    Outline and Installation Dimension

    CJX2-D-4CJX2-D-4
    Type A A' B   C   C′ a b1 b2 Φ Mounting mode
    A9-9,12,16 44  12.5  74  74  102  35  60  50  4.5  Screw installation or TH75 mounting rail installation
    A9-26 54  12.5  90  93.5  120.5  45  80  70  4.2 
    A9-30,40 54  12.5  90  108.5  135.2  45  80  70  4.2 
    A9-50,63,75 70  12.5  110    108    135  60  100  90  6.2  Installation or TH35 or TH75 mounting rail installation
    A9-95,110 90  12.5  148.5  123.5    151  78  136  126  6.2  Screw installation or TH75 mounting rail installation
    A9-145,185 Note:Refer to drawing 6 for dimension
    A9-210,260,300 Note:Refer to drawing 7 for dimension